40

Command Set

3.16 Current Readback

@Description

Read the estimated current output value at the specified analog output
module.

@Syntax

$(Addr)8

$

Command leading code. (1-character)

(Addr)

Address ID. (2-character)

6

Function code of last value readback.
(1-character)

@Response

!(Addr)(Data)

or

?(Addr)

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

(Data)

The current analog output value, the data format
depends on module configuration.

@Example

User command:

$088

Response:

!0802.000

This analog output module return the latest output value is 2.000 mA at
address 08H, if data format is engineering units and the signal range is
0~20mA.