beautypg.com

ADLINK ND-6013 User Manual

Page 97

background image

Data Format and Input Range

89


Two’s complement hexadecimal: CD27
((-2/5) x 32768) = -13107.2 = CD27H

Example 3:

Input Range is

±10 V

Input is +4 Volts


Two’s complement hexadecimal: 3333
((4/10) x 32768) = 13107.2 = 3333H

Example 4:

Input Range is Type K thermocouple (range 0

°C to 1000°C)

Input is 406.5

°C


Two’s complement hexadecimal: 3408
((406.5/1000) x 32768 ) = 13320.2 = 3408H

Ohm

Data format bit 1 and 0 set to 11 is ohm presentation.

This data format including three components.

1. sign (+)
2. digits
3. decimal point

Data is sign (+) followed with 5-digits and a decimal point

It does not exceed 7-characters

Maximum resolution is 0.01ohm, the decimal point is fixed


Example 1:

Input Range is Pt-100, -100

°C to +100°C, α=0.00385

Input is 120.23 ohm


ohm: +120.23