beautypg.com

36 set low alarm – ADLINK ND-6013 User Manual

Page 82

background image

74

Command Set

3.36 Set Low Alarm

@Description

Set low alarm limit value at specified analog input module.

@Syntax

@(Addr)LO(Data)

@

Command leading code

(Addr)

Address ID

LO

Set low alarm limit value.

(Data)

Alarm low limit value.
Data format is engineering units. (an + or - sign with
five decimal digits and a decimal fixed point.

@Response

!(Addr)

!

Command is valid.

(Addr)

Address ID.

@Example

User command:

@06LO+100.00

Response:

!06


Set low alarm limit value to +100

°C to accept J-type thermocouple input

at address 06H.

(6011/D, 6012/D, 6014D)