3.11 Span Calibration

@Description

To correct the gain errors of AD converter by using the span calibration.

@Syntax

$(Addr)0

$

Command leading code (1 character)

(Addr)

Address ID (2 character)

0

Span calibration (1 character)

@Response

!(Addr)
or
?(Addr)>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

@Example

User command:

$060

Response:

!06


To perform the span calibration for analog input module, address ID is
06H.

Note:

To perform the calibration, a proper input signal should be
connected to the analog input module. Different input range
have different input voltage, detail refer chapter 5 “Calibration”.

(6011/D, 6012/D, 6013 C4.6

6014D, 6017, 6018)