20

Introduction

1.7 Overview

of

NuDAM-6018

What is NuDAM-6018 ?

NuDAM-6018 is a thermocouple input module with 8 input channels.
Six of the eight channels are differential type and the other two are
single ended type.

Features of NuDAM-6018

8 analog input channels

6 differential inputs and 2 single ended inputs

Programmable input voltage range

Programmable host watchdog timer for host failure protection

On board CJC for temperature measurement

2500 Vrms isolation voltage

Internal watchdog timer for device failure protection

Easy programming by software

Easy installation and wiring

Wiring open detection

(5)

Specifications of NuDAM-6018

—

Interface

Interface: RS-485, 2 wires

Speed (bps): 1200, 2400, 4800, 9600, 19.2K, 38.4K ,115.2K
(115.2K only for firmware reversion above A4.00)

—

Analog Input

(6)

Input type: Differential input

Channels Numbers: 8

Resolution: 16 bits

Unit Conversion: Thermocouple, mV, V or mA

Thermocouple Type: J, K, T, E, R, S, B, N, C

J: 0

°C~760°C K:

0

°C~1370°C

(6)

T: -100

°C~400°C E:

0

°C~1000°C

R: 500

°C~1750°C S:

500

°C~1750°C

B: 500

°C~1800°C N:

-270

°C~1300°C

C: 0

°C~2320°C

Voltage Range: Programmable 6 levels ±2.5V, ±1V, ±500mV,
±100mV, ±50mV, ±15mV

Current Measurement: ±20mA (with external 125

Ω resistor)

—

Power

Power supply: +10V to +30V

Current consumption: 0.9 W

Note

(5)