Pressure Testing Fireplace Gas
Connections
1. Open equipment shutoff valve (see Figure 21).
2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP sup-
ply tank valve.

3. Make sure control knob of fireplace is in the

OFF position.

4. Check all joints from equipment shutoff valve

to gas control valve (see Figure 22 or 23).
Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Light fireplace (see Operating Fireplace,

pages 17 and 18). Check all other internal
joints for leaks.

7. Turn off fireplace (see To Turn Off Gas to

Appliance, page 18).

INSTALLATION

Continued

Equipment Shutoff Valve

Propane/LP
Supply Tank

Figure 21 - Equipment Shutoff Valve

ON

POSIT

O

POS

Open

Closed

Equipment
Shutoff
Valve

Figure 23 - Checking Gas Joints

(Propane/LP Gas Only)

Gas Control Valve

Figure 22 - Checking Gas Joints (Natural

Gas Only)

Equipment
Shutoff
Valve

Gas Meter

Gas Control Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal
and external to unit, for leaks
after installing or servicing. Cor-
rect all leaks at once.

WARNING: Never use an

open flame to check for a leak.
Apply a noncorrosive leak de-
tection fluid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.

Pressure Testing Gas Supply Piping
System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect fireplace with its appliance main

gas valve (control valve) and equipment
shutoff valve from gas supply pipping. Pres-
sures in excess of 1/2 psig will damage fire-
place gas regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve lo-
cated on or near gas meter for natural gas, or
by using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all
joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fit-
tings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG
(3.5 kPa)

1. Close equipment shutoff valve (see Figure 21).
2. Pressurize supply piping system by either

opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve lo-
cated on or near gas meter for natural gas, or
using compressed air.

3. Check all joints from gas meter for natural or

propane/LP supply to equipment shutoff valve
(see Figure 22 or 23). Apply noncorrosive leak
detection fluid to all joints. Bubbles forming
show a leak.

4. Correct all leaks at once.