beautypg.com

Bryant GAS-FIRED 454 User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Cycle of Operation

VIII. BALANCING THE SYSTEM

The 36-454 is equipped with a fan/pump motor

control (Bryant Model 821), an auxiliary

SPST relay and a sail switch. The fan/pump

motor control is a single pole, single throw

low voltage switch actuated by a heat motor

(low voltage electric resistance coil fastened

to mono-metal strip next to the switch). When

the thermostat calls for cooling, electric

current energizes the resistance coil in the

Model 821 control and in approximately one

minute the low voltage switch closes, ener­

gizing the auxiliary relay which starts the

condenser fan motor and solution pump-water

pump motor. The opening of the gas valve

will be delayed slightly until the condenser

fan is moving a sufficient amount of air

through the unit to activate the sail switch.

On shutdown by the thermostat, the gas valve

will close immediately; however, the balance

of the unit will continue to run for ap­

proximately 3 minutes until the low voltage

switch in the Model 821 control opens.

V I I . ADJUST GAS INPUT

The gas input must be checked and adjusted if

necessary to agree with the input shown on

the unit's rating plate.

The natural gas units are equipped with ad­

justable gas pressure regulators set at

factory for 4.2 inches w.c. manifold pres­

sure .

units by the following

Check natural

method:

gas

1. Measure gas at meter. Be sure all other

gas appliances are turned off. Increase or

decrease input to burners by adjusting the

gas pressure regulator.
Caution: The unit may be run for short

periods with the panel removed. Prolonged

operation with panels removed should not be

attempted.

After the unit is in operation and the input

has been measured and adjusted to agree with

the rating plate requirements, the system

must be balanced.

Any approved method of checking the air flow

over the water coil may be utilized. Refer to

the Bryant Service Manual on Gas Air Con­

ditioners for a review of standard methods.

IX. FREEZING WEATHER PROTECTION

Gas

Air Conditioner

The unit has built-in freeze protection suf­

ficient to protect the chiller and pump.

Chilled Water Pipes

If hard pipe (non-plastic) is used for thé

chilled water lines, it will be necessary to

drain the lines or add antifreeze . The recom­

mended antifreeze is Zerex. The chilled

water additive must be used in the same

proportion as indicated in Section V when

antifreeze treatment is required.

Chilled Water Coil

Chilled water coils cannot be completely

drained; therefore, if the water coil is sub­

ject to freezing temperatures, protect it by

adding antifreeze. The chilled water additive

must be used in the same proportion as indi­

cated in Section V when antifreeze treatment

is required.

Operation at Freezing Temperatures

The unit cannot be operated at temperatures

below 40° F.

36/454

-

8

-