beautypg.com

Warning, Installing infinity control, Ccui d 01 -- b – Carrier Infinity SYSTXCCUID01- B  User Manual

Page 4: Fig. 10 -- decorative backplate assembly, Fig. 11 -- universal four--wire connection diagram

background image

4

A03192

Fig. 10 -- Decorative Backplate Assembly

INSTALLING INFINITY CONTROL

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury,

death or equipment damage.
Before installing, modifying, or servicing system, the main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

!

WARNING

1. Turn off all power to equipment.
2. If an existing User Interface or control is being replaced:

a. Remove existing control from wall.

b. Disconnect wires from existing control.

c. Discard or recycle old control.

NOTE: Mercury is a hazardous waste, if existing control contains
any mercury, it MUST be disposed of properly. The User Interface
does not contain mercury.

3. Select Infinity Control mounting plastic (recess mount or

surface mount and decorative backplate if desired).

4. Route wires through large hole in mounting plastic. Level

rear plastic against wall (for aesthetic value only -- Infinity

Control need not be level to operate properly) and mark
wall through two mounting holes.

5. Drill two 3/16” (4.8 mm) mounting holes in wall where

marked.

6. Secure mounting plastic to wall using two screws and an-

chors provided.

7. Adjust length and routing of each wire to reach each wire

entry on the connector backplate. Strip 1/4” (6.4 mm) of in-
sulation from each wire.

8. Match and connect thermostat wires to proper terminals on

User Interface backplate. See wiring diagram Fig. 11, 12,
and 13.

A

B

C

D

A

B

C

D

User Interface

Green

Yellow

White

Red

OAT

Optional Remote

Room Sensor

HUM

COM
24V

Humidifier

Connection

S2

S1

A

B

C

D

ABCD

Connections

Communicating

AC or HP

Green

Yellow

White

Red

OAT

Sensor

(Optional)

Variable-Speed

Furnace/ Fan Coil

A03146

Fig. 11 -- Universal Four--Wire Connection Diagram

A

B

C

D

A

B

C

D

C

Y

ABCD

Connection

User Interface

1-Spd.
Non-Communicating
AC

Green

Yellow

White

Red

Optional Remote

Room Sensor

HUM

COM

24V

Humidifier

Connection

Y/Y2

S2

S1

OAT

OAT

Sensor

Variable-Speed

Furnace/Fan Coil

A07022

Fig. 12 -- Connection Diagram for Furnace or FE Fan Coil

w/1--Stage AC

A

B

C

D

A

B

C

D

ABCD

Connection

User Interface

1-Spd.
Non-communicating
HP

Green

Yellow

White

Red

Optional Remote

Room Sensor

HUM

C

Humidifier

Connection

Y

S2

S1

W2

Y

O

C

R

O

R

W

OAT

OAT

Sensor

Variable-Speed

Fan Coil

G

A07023

Fig. 13 -- Connection Diagram for FE Fan Coil with

Non-- Communicating 1--stage HP

A — Green = Data A
B — Yellow = Data B
C — White = 24VAC (Com)
D — Red = 24VAC (Hot)
NOTE: It is not mandatory that the above color code be used, but
each ABCD connection in the system MUST be wired consistently.
A separate ABCD Connector comes inside packaging and should

CCUI

D

01

--

B