Setup -- Hybrid Heat

HYBRID HEAT SETUP

FURNACE
LOCKOUT:

> 30 F

HEAT PUMP
LOCKOUT:

< 15 F

DEFROST W/FURNACE:

YES

< BACK

HP TO FURNACE
STAGE TIME:

15 MIN

OUTSIDE LOCKOUT TEMPS

A07030

Fig. 28 -- Hybrid Heat Setup

FURNACE LOCKOUT -- Temperature above which only the heat

pump will operate, except for defrost.

S

Default = NONE

S

Available settings = NONE thru >55_F / 13_C

HEAT PUMP LOCKOUT -- Temperature below which only the

furnace will operate.

S

Default = NONE

S

Available settings = NONE thru <55_F / 13_C

DEFROST W/FURNACE -- Choose whether furnace operates

during defrost cycle.

S

Default = YES

S

Available settings = YES / NO

HP TO FURNACE STAGING TIME -- Adjust the minimum
amount of time the heat pump will run before furnace will be

allowed to run.

S

Default = 15 MIN

S

Available settings = 15--60 minutes. If a demand of 5_F / 3_C or
greater exists, the timer will be overridden.

Setup -- Hydronic Heat

HYDRONIC HEAT SETUP

AIRFLOW:

800 CFM

BLOWER ON DELAY:

30 SEC

HOT WATER
LOCKOUT:

> 30 F

HEAT PUMP
LOCKOUT:

< 45 F

DEFROST W/WATER:

YES

BLOWER OFF DELAY: 30 SEC

< BACK

A07031

Fig. 29 -- Hydronic Heat Setup

HOT WATER LOCKOUT -- Outside temperature above which the

hot water will not operate except for defrost (if needed).

S

Available settings -- NO, 5 to 55_F / --15 to 13_C in 1_
increments

HEAT PUMP LOCKOUT -- Outside temperature below which
only the hot water will run, 1_F / .6_C resolution.

S

Appears only with a heat pump outdoor unit.

S

Available settings -- NO, 5 to 55_F / --15 to 13_C in 1_
increments

DEFROST W/WATER:

S

Available settings: YES / NO (Default =YES)

S

Appears only if heat pump is available If no, hot water will not
run during a defrost.

AIRFLOW -- Selects desired airflow during Hydronic Heating

S

Available range from OFF, 500 CFM(minimum) to 400
CFM/ton cooling maximum in 50 CFM increments.

S

Default is the cooling airflow. (350 CFM/ton)

S

OFF selection does not turn off airflow if heat pump is
defrosting.

BLOWER ON DELAY -- Time after hot water is requested that the

blower will turn on.

S

Available settings -- 0 to 240 seconds in 30 second increments

S

Default is 30

BLOWER OFF DELAY-- Time after hot water request terminates
before the blower will turn off.

S

Available settings -- 0 to 240 seconds in 30 second increments

S

Default is 0.

Setup -- Accessories

Filter Type:

S

MEDIA (i.e. TrueSenset)

S

EAC

S

MEDIA+EAC (i.e. TrueSenset)

CLEAN INTERVAL: 30 to 180 days (of actual blower operation).

(Default = 90)
Interval at which the Clean Filter notification will turn on. Applies

to EAC filter selection only.
Humidifier Installed:

S

NO

S

YES

If YES, indicates to the system whether a humidifier is installed

and enables humidification functions.
CHANGE PAD INTERVAL: 1 to 24 months (default=12 months)
Interval at which the Change Humidify Pad notification will be
displayed.
HUMIDIFY WITH FAN: (Heating Mode Only)

S

NO (default)

S

YES

If YES, the humidifier will turn on if there is a humidify demand
present. The fan will turn on to Low speed if the fan setting is

Auto.
Ventilator:
NOTE
: Only appears if ventilator is installed.
CLEAN INTERVAL:

S

60 to 180 days of actual operation (default=90)

Interval at which the Clean Ventilator Pre--filter notification will
turn on.
UV Lights Installed

S

NO

S

YES

If YES, indicates to the system whether UV lights are installed.
CHANGE INTERVAL:

S

6 to 48 months operation time (default=12 months)

Interval at which the Change UV Lights notification will be
displayed.

Setup -- System Maintenance

Remind Owner of Routine Maintenance Every:
This setup is used to adjust the timer interval in which the normal

System Maintenance notification is turned on for the homeowner.
(See Fig. 30.)
Range =

S

OFF

S

6 to 24 months, (default=12 months)