Section 3 — M aintenance
Guardian Air-cooled 6 kW, 8 kW and 10 kW Generators
MAINTENANCE
3=^
3.12 SERVICE SCHEDULE
ATTENTION: It is recommended
that
all service work
be performed by your nearest Generac/Guardian Authorized Dealer.
SYSTEM/COMPONENT
PROCEDURE
FREQUENCY
X = Action
R = Replace as Necessary
* = Notify Dealer
if Repair is Needed.
Inspect
Change
Clean
W = Weekly
M = Monthly
Y = Yearly
H = Hours
FUEL
Fuel lines and connections*
X
M
LUBRICATION
Oil level
X
M •
Oil
X
FIRST 9 H,
EVERY 100 H AND Y
Oil filter
X
FIRST 9 H,
EVERY 200 H AND Y
Oil line leakage*
X
100 H
COOLING
Enclosure louvers
X
X
W
EXHAUST LINE
Exhaust outlet
X
X
W
Spark arrestor*
X
Y
BATTERY
Remove corrosion,
ensure dryness
X
X
M
Clean and tighten
battery terminals
X
X
M
Check charge state
X
R
EVERY 6 M
Electrolyte level
(unsealed batteries only)*
X
R
EVERY 6 M
ENGINE AND MOUNTING
Air cleaner
X
R
100 H AND Y
6 kW foam
precleaner
X
EVERY 25 H OR
EVERY 3 M
Spark plug(s)
X
R
100 H AND Y
GENERAL CONDITION
Vibration, Noise, Leakage,
Temperature*
X
M
COMPLETE TUNE-UP*
TO BE COMPLETED BY A GENERAC/
GUARDIAN AUTHORIZED DEALER
Y
Generac” Power Systems, Inc. i S