beautypg.com

Carrier 19DG User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Oil Heater

— Energize’ the oil heater to minimize

absorption of refrigerant by the oil. An indicator
light (Fig. 1) goes on when the oil heater is
energized. Set the oil heater thermostat to main­

tain a minimum oil reservoir temperature of 145 F
at shutdown.

Charging Refrigerant

— Proceed as follows.

1. Install a charging valve on the 3/4-m. drum

opening as shown in Fig. 2. When the 3/4-in.
pipe nipple is screwed in, the nipple forces the
bottle cap off its seat.

2. Connect a short piece of plastic hose or copper

tubing from drum valve to the cooler charging
valve located beside the float chamber (Fig. 1).

3.

Circulate chilled water during the charging

process.

4.

At a vacuum of IS in. Hg or greater, liquid

Refrigerant 1 i will flash mto gas and may
cause tube freeze-ap. If machine vacuum is

18 in. Hg or greater, keep refrigerant drum

upright, open valves and admut refrigerant to

cooler as a gas until machine vacuum is ies.s =
than 18 m. Kg.

5. The refrigerant supplied with the machine is in

excess of that required for initial charging.
Charge only that amount shown in Table 1 The
machine under vacuum will draw refrigerant
from the drum.

6. After the machine has been started, it may be

necessary to adjust the refrigerant charge for
optimum

machine

performance.

Refer

to

Trimming Refrigerant Charge (page 7) for full

load adjustment.

Table 1 — Charging Quantity

SIZE*

WEIGHT

(lb R-11)

SIZE*

WEIGHT

(lb R-11)

SIZE*

WEIGHT
(lb R-11)

19DG11

400

19DG21

525

19DG33

760

19DG13

400

19DG23

550

19DG35

800

19DG15

425

19DG25

575

19DG36

925

19DG17

450

19DG27

575

19DG37

985

19DG20

525

19DG31

725

19DG39

960

Check Operation of Safety Controls

— As checks

are made, the control panel lights should appear as
indicated.

1. Open main disconnect (all power off to starter

and controls). Then disconnect main motor
leads in starter.

2. Provide control circuit power.

CONTROL LIGHTS

□ OFF

a

n

1

2

3

4

5

6

7

8

ON-STOP

START

OIL PUMP

POWER

SAFETY CIRCUIT

LOAD RECYCLE

PROGRAM TIMER

*Unishe(i Size

• Sec lower right corner of machine identification

plate (Fig 1)

3. Press ON-STOP button (light goes on). If

SAFETY CIRCUIT light does not go on, check

resets on condenser high-pressure safety, low-
refrigerant safety, bearing and motor high-

temperature circuit breakers and compressor
overloads in starter. Check 3-amp fuse in
control center.

If SAFETY CIRCUIT light goes on but LOAD
RECYCLE light stays off, check the chilled
water recycle switch (Auto.-Reset).

If both lights go on, manually trip and reset

motor and bearing high-temperature circuit

breakers, compressor motor overloads in
starter, low-refrigerant temperature cutout and

high-condenser cutout to be sure they cut off
the safety light. Tripping the chilled water
recycle switch will cut off the LOAD RE­
CYCLE light only.

4.

Press ON-STOP button (light goes out).

Remove and tag gray striped wire running

between terminal [1^ and Vl_ in control
center.

5.

Start chilled water and condenser water

pumps. Press ON-STOP button (light goes on).

6. Press OIL PUMP button for several seconds.

Pump should raise oil pressure to 20-25 psi
differential between pump discharge gage on

control panel and oil reservoir gage. SAFETY

CIRCUIT and LOAD RECYCLE lights should
go on.

7. Release OIL PUMP button. SAFETY CIR­

CUIT and LOAD RECYCLE lights should go
out.