beautypg.com

Table 3 — checking safety controls (cont), Setting operating controls – Carrier 19EA User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 3 — Checking Safety Controls (cont)

SAFETY OR CONTROL DEVICE

3. Low Oil Pressure Cutout (Fig. 3)

RANGE
DIAL ADJUSTMEN1?
REMOVE METAL

COVER

DIFFERENTIAL

OIL

PRESSURE

4. Economizer Cooler Differentia! Pressure

Switch {Fig. 3)

Ù .

i. Condenser High-Pressure Cutout (Fig. 3)

range

adjustment

SCREW

6. Cooler Low-Pressure Cutout (Fig. 3)

RECOMMENDED SETTING

Factory set to cut out at 13 ±1 psi differential Operate oil pump manually
Remove cap and gasket from regulating valve (item 18, Fig 1) Loosen locknut

Turn adjusting screw counterclockwise to lower oil pressure to 12 psi differential

If safety does not trip, turn range dial clockwise until cutout occurs Access to

control is thru knockout at rear of control box

'<7

The economizer-cooler differential pressure switch is factory set to energize the
refrigerant feed control at 10 psid

The condenser high pressure switch is factory set to shut machine down when
condenser pressure reaches 161 ±5 psig Field calibration is not required

Cooler low-pressure switch is factory set at 32 ±2 psig If design suction
temperature is below 36 F, field resetting may be necessary With control power

off (power light out), install jumpers between terminals

and 0 and

between

and

. Set switch to cut out at one degree below design

suction temperature Remove jumpers Restore power

Setting Operating Controls

MOTOR CURRENT CALIBRATION
PROCEDURE

design leaving chilled water temperature and

1. Establish a steady motor cun'ent value for this

calibration.

Open

guide

vanes

manually

(capacity control to “Inc”) until full load
current is reached. Motor current calibration

adjustment (item 1, Fig. 3) may have to be
turned counterclockwise to permit vanes to
open further. Do not exceed 105 percent of

nameplate full load amps

If building load is sufficient to maintain full
load current for a period of time, calibrate at
this condition. With small loads, pull down to

and maintain (capacity control to “Hold”)

calibrate at this condition.

2. Measure motor current at selected condition.

Determine its percentage of full load motor
current.

3. Use this percentage figure to set the electrical

demand adjustment (item 3, Fig. 3) per the
following table:

Percent of Full

Load Motor Current

105

85 or above

65 to 84

45 to 64
below 45

Electrical Demand

Adjustment Setting

1ÜÜ pêrcêrvF ~

80 percent
60 percent
40 percent

Control cannot be
calibrated