Trouble analysis chart – Carrier 38GNA User Manual
Page 7
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Trouble Analysis Chart
SYMPTOM
CAUSE
REMEDY
Compressor and condenser fan do
not start
Power failure
Call power company
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker
Defective thermostat contactor or con
trol relay
Replace component
Low-line voltage
Determine cause and correct
Incorrect or faulty wiring
Check wiring diagram and rewire cor
rectly
Thermostat setting too high
Lower thermostat setting below room
temperature
Compressor does not start, but con
denser fan runs
Faulty wiring or loose connections in
compressor circuit
Check wiring; repair or replace
Compressor motor burned out, seized,
or internal overload open
Replace compressor and determine
cause
Defective run capacitor
Determine cause and replace
Compressor cycles (other than nor
mally satisfying thermostat)
Refrigerant overcharged or under
charged
Remove refrigerant, evacuate system,
and recharge
Defective compressor
Determine cause and replace
Low-line voltage
Determine cause and correct
Blocked condenser
Determine cause and correct
Defective run capacitor
Determine cause and replace
Defective thermostat
Replace thermostat
Faulty condenser fan motor or capacitor
Replace
Restriction in refrigerant system
Locate restriction and remove
Compressor operates continuously
Unit undersized for load
Decrease load or increase unit size
Thermostat setting too low
Raise thermostat setting above room
temperature
Low refrigerant charge
Locate leak; repair and recharge
Leaking valves in compressor
Replace compressor
Air in system
Remove refrigerant, evacuate system,
recharge
Condenser coil dirty or restricted
Clean coil or remove restriction
Excessive head pressure
Dirty condenser coil
Clean coil
Refrigerant overcharged
Remove excess refrigerant
Air in system
Remove refrigerant, evacuate system,
and recharge
Condenser air restricted or air short cy
cling
Eliminate cause
Head pressure too low
Low refrigerant charge
Locate leak; repair and recharge
Compressor valves leaking
Replace compressor
Restriction in liquid tube
Remove restriction
Excessive suction pressure
High-heat load
Check for source and eliminate
Compressor valves leaking
Replace compressor
Refrigerant overcharged
Remove excess refrigerant
Suction pressure too low
Low refrigerant charge
Locate leak; repair and recharge
Metering device or low side restricted
Remove source or restriction
Low evaporator air
Increase air
Temperature too low in conditioned
area
Reset thermostat