beautypg.com

Step 1—make opening in wall, Step 2—make piping connections – Carrier 38GNA User Manual

Page 2

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

AIR OUT

7/8 DIA HOLE & 1-3/32 DIA K.O.

POWER INLET

A75135

Fig. 1—Dimensions and Connections

Fig. 2—Roughing-ln Supporting Frame

Step 1—Make Opening in Wall

Make an opening approximately 26-1/2 x 29 in. in a wall as close

to the cooling unit as possible. Build a frame to support the

condensing unit. (See Fig. 2.)

1. Insert condensing unit with frame into the wall opening.

2. Extend unit approximately 1 in. beyond outside (finished) wall

and tilt to the outside to allow rainwater to drain off. (See Fig.
3.)

3. Fasten unit to frame with metal straps.

4. Use flashing under unit and caulk all edges to provide

weathertight seal. (See Fig. 3.)

Step 2—Make Piping Connections

SELECT

CORRECT

LIQUID

AND

SUCTION

LINE

LENGTHS/DIAMETERS - Refer to Table 2.

INSTALL REFRIGERANT LINES — The condensing unit is

fully charged at the factory. Be sure both service valves are front

seated (turned clockwise) to avoid loss of charge.

Do not remove

refrigerant line connection seals from condensing unit, matching
coil, or refrigerant tubing until ready to make actual connection at

point of seal.

(M>