beautypg.com

Electrical data and wiring – Carrier 50MQ User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

ELECTRICAL DATA AND WIRING

Field wiring must comply with local and

national fire, safety and electrical codes. Voltage to
unit must be within ±10% of voltage indicated on
nameplate. On 3-phase units, phases must be
balanced within 2%.

Operation of unit on improper line voltage or ;
with e.xcessive phase unbalance constitutes
abuse and is not covered by Carrier Warranty.

See Table 2 for recom m ended wire and fuse sizes

Step 7 — Install a Branch Circuit Fused Disconnect

of adequate size to handle unit starting current.
Locate disconnect within sight of and readily
accessible from the unit. (Use a separate fused
disconnect(s) for each electric circuit as required.)

Step 8 — Bring Line Power Leads Into Unit.

Extend leads from fused disconnect thru hole pro­

vided (Fig. 1) into line wiring splice box (Fig, 5).

Step 9 — Connect Ground Lead to Ground Lug in
Splice Box

before connecting power wiring. See Fig.

6. Connect line power leads to yellow and black
pigtails on single-phase units or yellow, blue and
black pigtails on 3-phase units. Use wire nuts

'provided. Tape each connection. Wire nuts are

suitable for copper or aluminum wire since they
contain joint compound.

Step 10 — Set Indoor Fan Motor Speed

— (Refer

to page 2 for minimum allowable air quantity for
safe electric heater operation). Four-speed indoor
fan motor is factory wired for high speed opera­
tion. Fan motor is equipped with spade-type speed
selector terminals marked 1, 2, 3 and 4. For lower

fan speed, remove black

unit

lead from motor

spade terminal 1 and connect to spade terminal 2,
3 or 4. On alternate fan motors remove black

m otor

lead from unit connection and replace with

blue, orange or red motor lead.

MOTOR LEAD

MOTOR TERMINAL

FAN SPEED

Black

H i g h

B lue

2

Medium

H i g h

Orange

Red

3

4

Med ium

Low

Low

Step 11 — Control Power Wiring (24 v)

is brought

through 7/8-in. hole provided in unit. Fig. 1.

Extend leads to unit control wiring terminal board.
Fig. 5. Connect leads to terminal board as directed
in Fig. 7.

HEATER

INSTALLATION

AREA

INDOOR FAN MOTOR

CONTROL WIRING
TERMINAL BOARD

WIRING KNOCKOUTS

■AND HOLES

(HIDDEN) SEE FIG t

LINE WIRING

SPLICE BOX

LINE VOLTAGE PIGTAILS

Fig. 5 — Unit Wiring Terminal Location

Table 2 — Unit Electrical Data

OPER

MODEL

V/PH

VOLTAGE*

Max

Min

50MQÒ22

50MQ027
S0MQ032
50MQ037

200/1

220

180

50MQ022
50MQ027
50MQ032
50MQ037

230/1

254

207

50MQ032

200/230/3

254

180

50MQ037

200/230/3

254

180

COMPRESSOR

IFM

OFM

BRANCH CIRCUIT

Power

Max

Gnd

Max

LRA

FLA

FLA

FLA

Wire

Ft

Wire

Fuse

Size

W ire

Sizet

Amps

(AWG)

(AWG)

75

14.1

2 2

2.2

10

40

10

35

80

16.2

2.2

2.2

10

35

10

40

99

20.8

3.6

2 2

8

43

10

50

112

26.5

3.9

2.2

8

35

10

60

68

12 8

2.0

1 9

12

32

12

30

72

14 0

2.0

1.9

10

47

10

35

88

18 0

3 1

1 9

10

36

10

45

100

23.0

3.4

1.9

8

45

10

50

75

13.0/11.5

3.6/3.1

2.2/1.9

10/12

50/42

10/12

35/30

80

15.0/12 8

3.9/3.4

2.2/1.9

10/10

45/60

10/10

35/30

FLA

— Full Load Amps

LRA

— Locked Rotor Amps

IFM

— Indoor Fan Motor

OFM

— Outdoor Fan Motor

"Permissible limits of the voltage range at which the units will

operate satisfactorily.

tRequIred when using nonmetallic conduit.

N O T E S :

1. Fan motors are 200w or 230-v, single-phase.

2. All units equipped with 24-v transformer for external control circuit.
3. Copper wire sizes based on 60 C. Aluminum field wiring may be used

when spiice connected to copper pigtails from unit with factory-
supplied wire nuts. Use latest National Electrical Code for aluminum
wire sizing.