beautypg.com

A warning, Refrigerant charging (refer to fig. 6 and table 5), A caution – Carrier 38EN User Manual

Page 4: Step 5 — start-up, 38en air-cooled condensing units

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING A COOLING

38EN

Air-Cooled Condensing Units

INSTALL BRANCH CIRCUIT DISCONNECT PER

NEC of adequate size to handle unit starting current.

Locate disconnect within sight from and readily acces­

sible from unit, per Section 440-14 of National Electrical

Code (NEC).
ROUTE LINE POWER LEADS — Extend leads from

disconnect through power wiring hole provided (see

Fig. 1) and into unit splice area. Remove control box

cover to gain access to unit wiring.

CONNECT GROUND LEAD AND POWER WIRING

— Connect ground lead to ground connection in control
box for safety. Then connect power wiring. See Fig. 4.
Splice line power leads to yellow and black pigtails. Use
wire nuts and tape at each connection. Connect unit
wiring to copper power wiring only.
CONNECT CONTROL POWER WIRING — Route
24-v control wires through control wiring hole and
connect to pigtails supplied with unit (Fig. 1). Splice

control leads to brown and blue pigtails on all units.

See Fig. 5.

Use furnace or fan coil transformer as 24-v (40-va

minimum) supply for system as shown in Fig. 5, or use

accessory transformer (refer to Service Data).

NOTE: Some 38EN units are equipped with a fan time

delay. This permits indoor fan to continue to operate for

90 seconds, which provides additional cooling after

compressor has eyeled off. Refer to separate installation
instructions packaged with fan time delay (shipped

with unit).

A

WARNING

To

avoid

personal

injury,

be

sure

indoor

blower has stopped before attempting service

or maintenance.

Refrigerant Charging (Refer to Fig. 6

and Table 5)

A

CAUTION

To prevent personal injury, wear safety glasses

and gloves when handling refrigerant. Do not

overcharge system. This can cause compressor

flooding.

I-PHASE
CONN. TO

DISCONNECT
PER NEC

-GROUND LEAD

-C®1

grounding

lug

-

— BLK----------------

YEL-

1- PHASE

COND UNIT

3-PHASE
CONN. TO

DISCONNECT

PER NEC

r__________________

BLK -

BLU-

• YEL -

--GROUND LEAD --J-SGROUNDING LUG

3-PHASE COND UNIT

fr-i

— SPLICE CONNECTIONS

-------------- FIELD WIRING

-------------- FACTORY WIRING

Fig. 4 — Line Power Connections

Table 4 — Service Data

Step 5 — Start-Up

1. Energize crankease heater a minimum of 24 hours

before starting unit. To energize heater only, set
thermostat at OFF position and close electrical dis­

connect to outdoor unit.

2. Backseat (open) liquid and suction line serviee valves.
3. Set thermostat selector switch at OFF.

4. Set room thermostat at desired temperature. Be sure

set point is below indoor ambient temperature.

5. Close electrieal diseonnects to energize system.
6. Set room thermostat at COOL and fan switch at FAN

or AUTO, as desired. Operate unit for 15 minutes.

Check system refrigerant charge. See Refrigerant
Charging, below.

Motors and controls are designed to operate satis-

faetorily in the voltage range shown in Table 3. If

necessary to use manifold gages for servicing, refer to
Carrier Standard Service Techniques Manual, Chapter 1,

Refrigerants, page 1 - 5, Fig. 8, for bypass method of

returning charge to system. Removal of liquid line

eharging hose without following these precautions could

result in some loss of charge.

MODEL

38EN

COMPRESSOR

OIL

CHARGE (oz)

R-22

CHG* (lb)

OUTDOOR

FAN RPM

Initial

Recharge

015300

REK3-0125-PFV

24

20

3 60

015310

AK8515E

17

15

3 20

018300

H21B193ABCA

40

37

3 60

1650

018310

RES3-0175

24

20

3 70

024300,

H21B243ABCA

40

37

3 80

310

030300

H21A313ABCA

40

37

5 60

030320

MD3215GG

46

44

6 70

036300,

H21A373ABCA

50

47

5 80

320

042300

H21A463ABCA

50

47

7 20

048300

PC5316BD

76

62

7 60

060300,

PC6716AG

76

62

9 60

310

PC6716AG

76

62

12.50

030500

H21A313DBD

40

37

5 60

036500

H21A373DBD

50

47

5 80

1100

042500

H21A463DBD

50

47

7 20

048500

PY5316AD

76

62

7 60

060500,

PY6716AF

76

62

9 60

510

PY6716AF

76

62

12.50

036600

H21A373DBE

50

47

5 80

042600

H21A463DBE

50

47

7 20

048600

PH5316AD

76

62

7 60

060600,

PH6716AF

76

62

9 60

610

PH6716AF

76

62

12 50

'Factory refrigerant charge is adequate when indoor unit and outdoor unit

are the same size and are connected with 25 ft or iess of fieid-suppiied

tubing of recommended size or Carrier accessory tubing

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book|1 |4

PC 101 Catalog No. 563-825 PrintedinUSA Form38EN-3SI Pg4 485

12-84 Replaces: 38EN-2SI