38EN

Air-Cooled Condensing Units

Table 1 — Physical Data (Refer to Fig. 1)

MODEL 38EN

015

018

024

030

036

042

048

060

OPER WT (lb)*

94

111

111

142

146

182

200

228

REFRIGERANT

Control

22

AccuRater'“ (Installed In I.D. Coil)

COND FAN

Air Discharge

Air Qty (cfm)

Motor Rpm (60 Hz)

Propelle

1950
1650

ir Type, Direct Drive

Vertical

2800 1 4800

1100

COND COIL (fins/in.)

Tube Diam

Rows
Face Area (sq ft)

Outer Row

Inner Row

20

% in -

8 15

'/2

1

12 37

16

in , E-coil

17 11

2

17.11

DIMENSIONS (ft-in.)

Diameter A
Height B

1- 5'/2

2- 1

1-9’/2

2-5'/4

2-7

CONN (in. ODF)

Suction

Liquid

Compatible F

%

tting (Suction and Liquid)

%

%

REFRIG LINES (in. ODF)

Suction
Liquid

%

1

%

1 '/e 1

1’/at

%

*Add 10 lbs for louvered casing (If so equipped) Weight Increases slightly

with addition of any accessories

t38EN048,060 require a I'/s-ln suction line for optimum performance. A

%- X 1'/8-in connection adapter accessory (Carrier Part No. 28AU900061)

is available If a %-in accessory tubing package is used, expect a 3%
capacity loss

A

CAUTION

DO NOT BURY MORE THAN 3 FT OF RE­

FRIGERANT TUBING IN GROUND. If any
section of tubing is buried, there must be a 6-in.

vertical rise to the valve connections on the outdoor

unit. If more than the recommended length is buried,

refrigerant may migrate to cooler buried section
during extended periods of unit shutdown, causing
refrigerant slugging and possibly compressor damage

at start-up.

RETAINER

FLARE NUT

FLARE
CONNECTION

Fig. 2 — AccuRater (Bypass Type)

Components

CUT HERE-J

,0-RING

Fig. 3 — Repair of Mechanicai Connection

CONNECT REFRIGERANT LINES to fittings on

outdoor unit suction and liquid service valves (Fig. 1).

Unit Compatible Fittings permit mechanical (quick-

connect) or sweat connections.

Models 38EN048,060 — When using 1-1/8-in. field-

supplied refrigerant suction line, sweat-connect suction
line to 1-1/8-in. end of required connection adapter.

Be sure to provide a heat sink at the service valve to

prevent damage during sweating operation. Connect

3/4-in. end of adapter to unit suction line Compatible

Fitting. Connect liquid refrigerant line to unit. When a

7/8-in. field-supplied suction line is used, provide a field-

supplied 3/4-in. to 7/8-in. suction line adapter (not
necessary if 38LS accessory tubing is used).

Table 2 — AccuRater™ Selection Chart

COND UNIT

38EN

ACCURATER'“ PISTON NO.

Evap Size (Coil or Fan Coil)

(1- and 3-Ph)

015

018

024

030

036

042

048

060

060

015-0

46

TXV

_

018-0

52

52

TXV

024-0

57

57

TXV

030-0

_

-

m

65

TXV

030-2

__

631

036-0

m

70

TXV

042-0

78

78

TXV

048-0

060-0

060-1

98

Factory-installed

piston

Obtain

replacement

pistons

through local Carrier distributor