beautypg.com

User manual - optima ups 1k-3k (english) – XMART Optima 3K-HB User Manual

Page 7

background image

USER MANUAL - OPTIMA UPS 1K-3K (ENGLISH)

_________________________________________________________________________________________________________________________________

www.xmart-ups.com

1406-OPTIMA

1K-3K

- 7

4. INSTALATION

WARNINGS FOR FULL BRIDGE MODELS: (1KF to 3KF) & (1KF-CN to 3KF-CN)

FULL BRIDGE MODELS: For all full-bridge models (1KF-3KF & 1KF-CN to 3KF-CN), It is not allowed to connect output Neutral line to
input Neutral line. This practice can damage UPS. This kind of damage is not covered by warranty.

FIG-1

FULL BRIDGE MODELS: For all full-bridge models (1KF-3KF & 1KF-CN to 3KF-CN) it is not allowed to connect output Neutral to
system Ground. This practice will generate internal damage in the UPS. In full-bridge UPS output Neutral is not same than input
Neutral so a floating voltage will be generated between N-G at output side of the UPS. This voltage is not harmful for your equipment
connected to UPS. If you need 0Vac in N to G for your equipment, please check recommendation of FIG 3.
HALF BRIDGE models allow connection of their output Neutral line with system ground (G).

FIG-2


This manual is related to the following products: