SPECIFICATIONS (1KF / 2KF / 3KF) & (1KF-CN / 2KF-CN / 3KF-CN) (1/2)

OPTIMA (F) & (F-CN)


INPUT / ENTRADA

Freq. Range / Rango Frecuencia

Slew Rate / Seguimiento de F.
Surge Immunity Level

Output Regulation / Rango de Salida

Freq. Conversion / Conversión Frec.
EPO /Apagado Emergencia
Progammable Outputs / Salidas Prog.

Eco Mode

AC Mode / Modo Normal
Output Shortcircuit / Cortocircuito en Salida
Battery Mode / Modo Batería

Type / Tipo
Cap. & Qty
Recharge Time / Recarga
Charging Voltage / Voltaje de Carga
Charging Amps / Corriente de Carga
EXT. BATT CABINETS (Optional) - BATERIAS EXTERNAS (opcionales)
Standard EXT-BATT pack

ALARM / ALARMAS
Alarm Beep / Alarma Sonora:

Frequency / Frecuencia (Batt. Mode)

AC to Inverter / Tiempo AC a Inversor
Waveform / Forma de Onda

BATTERIES / BATERIAS

LCD

OVERLOAD/ SOBRECARGA

Current Crest Ratio / Factor de Cresta

Battery Mode / Modo Batería

INDICATORS / INDICADORES

OUTPUT / SALIDA

Phase / Fases
Power Factor / Factor de Potencia

ONLINE UPS (1/2)

Range / Rango - Vac (Models 120V):

Capacity / Capacidad (VA)

Voltage Output / Voltaje de Salida AC

Capacity / Capacidad (W)

Input THDi / THDi de Entrada

1600W

x

12V-9Ah x 12

12V/9AH x 6

Pure Sinewave / Sinusoidal Pura

N

N

1KF & 1KF-CN

2KF & 2KF-CN

Range / Rango - Vac (Models 220V):

Harmonic Distortion /
Dist. Armónica (THDv)

PEAK EFFICIENCY / EFICIENCIA MAX.

AC Mode / Modo AC

< 7% @ 100% load

1 Hz / s

3KF & 3KF-CN

1000VA

2000VA

3000VA

2400W

(*N1) Model 120V: 110/115/120/127Vac - Model 220V: 208/220/230/240Vac

+/-1%

> 88%

< 3% @ Linear Load / Carga Lineal

<6% @ No Linear Load / Carga no Lineal

> 90%

> 89%

0 ms

800W

12V/9AH x 4

1.0 A (Max.)

12V-9Ah x 8

40 Hz - 70Hz

Single phase with ground / 1 fase + Tierra

> 0.99 @ 100% load

> 93%

N

> 93%
> 89%

(*N3) 50 Hz +/- 0.25 Hz - 60Hz +/- 0.3 Hz

3:1 @ 100% load

N

12V/9AH x 2

> 86%

Model 120V: 80Vac-150Vac (@ 100% load)

Model 120V: 50Vac-150Vac (@ 50% load)

Model 220V: 160Vac-300Vac (@ 100% load)

Model 220V: 110Vac-300Vac (@ 50% load)

N

4 Hours for 90% capacity / 4 Horas para recuperar el 90% de carga

UPS status, Load level, Battery, Input/Output voltage, Discharge timer, and Fault conditions

Estado del UPS, Consumo, Baterías, Voltaje Entrada/Salida, Autonomía, Diagnostico Fallas

Battery Mode, Low batt., Overload, UPS Failure / Modo Batería, Baja batería, Sobrecargas, Falla

N

N

N

N

> 89%

> 93%

> 7KV (EN61000-4-5)

27.4Vdc

54.7Vdc

82.1Vdc

100%~110%: (warning-alarma) / 110%~130%: 30s: shutdown / >130% : 1s: shutdown

100%~110%: (warning-alarma) / 110%~130%: 1min: bypass / >130% : 1s: bypass

Full Protection for all outlets / Protección en todas las salidas

Sealed Lead Acid VRLA-AGM / Sellada de Libre Mantenimiento VRLA-AGM