3.4 TERMINAL DESCRIPTION

3.4.1 CONNECTOR 1

PIN No

DESCRIPTION

CABLE SIZE

NOTES

1

Plant supply negative

1.0mm

2

2

Plant supply positive

1.0mm

2

Recommended fuse 2A anti-surge

3

Digital input expansion 1

0.5mm

2

Requires a contact to plant supply
negative.

4

Digital input expansion 2

0.5mm

2

Requires a contact to plant supply
negative.

5

Digital input expansion 3

0.5mm

2

Requires a contact to plant supply
negative.

6

Digital input expansion 4

0.5mm

2

Requires a contact to plant supply
negative.

7

Digital input expansion 5

0.5mm

2

Requires a contact to plant supply
negative.

8

Digital input expansion 6

0.5mm

2

Requires a contact to plant supply
negative.

9

Digital input expansion 7

0.5mm

2

Requires a contact to plant supply
negative.

10

Digital input expansion 8

0.5mm

2

Requires a contact to plant supply
negative.

11

Analogue input expansion 1

0.5mm

2

Connect to plant supply negative if
unused

12

Analogue input expansion 1
return

0.5mm

2

Connect to plant supply negative if
unused

13

Analogue input expansion 2

0.5mm

2

Connect to plant supply negative if
unused

14

Analogue input expansion 2
return

0.5mm

2

Connect to plant supply negative if
unused

3.4.2 CONNECTOR 2

PIN No

DESCRIPTION

CABLE SIZE

NOTES

A

0V

0.5mm

2

B

A

0.5mm

2

C

B

0.5mm

2

D

+12V

0.5mm

2

Thinner cable will reduce the maximum
allowable cable length

CAUTION!: Connector 2 is only intended for connection to the DSE 549 annunciator.

Connection to any other device may cause damage and will invalidate the warranty.