Winco RDP-110 User Manual
Page 14
2-2
RDP-110 Human-Machine Interface
9318100990 Rev E
Silence
Alarm
Test
Lamp
Emergency Stop Activated
Sender Failure
Airbox Closed
Alarm Conditions
Overspeed
Overcrank
Low Oil Pressure
High Coolant Temperature
Low Coolant Level
Switch Not In Auto
Display
Remote
Panel
Battery Overvoltage
Battery Charger Failure
Pre Alarm Conditions
-
Weak Battery
Low Fuel Level
Low Oil Pressure
EPS Supplying Load
Low Coolant Temperature
High Coolant Temperature
Display Panel On
Ba
s
le
r
RDP 110
R
-
A
B
C
D
E
F
G
H
D2829-17
10-29-98
Figure 2-2. RDP-110 Front Panel (DGC-2000 Version)
Table 2-1. RDP-110 HMI (Controls and Indicators)
A
Green LED illuminates when power is applied to the RDP-110.
B
Green LED turns ON when the generator is supplying more than two percent of rated
current.
C
Pre-Alarm Conditions
• Yellow LED illuminates when the high coolant temperature pre-alarm setting is
exceeded.
• Yellow LED illuminates when the low coolant temperature pre-alarm setting is
exceeded.
• Yellow LED illuminates when the low oil pressure pre-alarm setting is exceeded.
• Yellow LED illuminates when the low fuel level pre-alarm setting is exceeded.
• Yellow LED illuminates when the battery overvoltage pre-alarm setting is
exceeded.
• Yellow LED illuminates when the weak battery pre-alarm setting is exceeded.
• Yellow LED illuminates when the battery charger failure contact has closed.
D Pushbuttons
Lamp Test Pushbutton exercises the audible alarm and tests all LED’s.
Alarm Silence Pushbutton silences the audible alarm.