beautypg.com

Functions, Specifications, Electrical – Winco RDP-110 User Manual

Page 10: Power input, Hardware, Communication port, Isolation, Radio, Environment, Functions -2 specifications -2

background image

1-2

RDP-110 General Information

9318100990 Rev E

FUNCTIONS

RDP-110 remote display panel displays the following functions:

Switch Not in Auto Alarm

Low Coolant Level Alarm

High Coolant Temperature Alarm

Low Oil Pressure Alarm

Overcrank

Alarm

Overspeed

Alarm

Emergency Stop Alarm

Airbox Closed Alarm for RDP-110 X2 or fuel leak/Sender failure for RDP-110 X1.

Sender Failure Alarm

Display Panel On LED

Emergency System Supplying Load LED

High Coolant Temperature Pre-alarm

Low Coolant Temperature Pre-alarm

Low Oil Pressure Pre-alarm

Low Fuel Level Pre-alarm

Battery Overvoltage Pre-alarm

Weak Battery Pre-alarm

Battery Charger Failure Pre-alarm

SPECIFICATIONS

RDP-110 Remote Display Panels have the following specifications.

Electrical

Power Input

DC Range

8 to 32 Vdc, 2 watts maximum

AC Range

84 to 144 Vac, 5 VA maximum

Hardware

Communication Port

Interface

RS-485

Used to communicate with DGC-2020, 500, 1000,
and 2000

Isolation

1800 Vdc for one minute between chassis
ground and ac voltage input. 700 Vdc for one
minute between any of the following groups

Chassis

ground

Battery and 485 terminals

AC voltage inputs

Radio Frequency Interference (RFI)

Type tested using a 5 watt, hand-held
transceiver operating at random frequencies
centered around 144 and 440 megahertz with
the antenna located within 6 inches (15
centimeters) of the device in both vertical and
horizontal planes

Environment

Operating Temperature Range

-40°C to 70°C (-40°F to 158°F)

Storage Temperature Range

-40°C to 85°C (-40°F to 185°F)