Functions, Specifications, Electrical – Winco RDP-110 User Manual
Page 10: Power input, Hardware, Communication port, Isolation, Radio, Environment, Functions -2 specifications -2
1-2
RDP-110 General Information
9318100990 Rev E
FUNCTIONS
RDP-110 remote display panel displays the following functions:
•
Switch Not in Auto Alarm
•
Low Coolant Level Alarm
•
High Coolant Temperature Alarm
•
Low Oil Pressure Alarm
•
Overcrank
Alarm
•
Overspeed
Alarm
•
Emergency Stop Alarm
•
Airbox Closed Alarm for RDP-110 X2 or fuel leak/Sender failure for RDP-110 X1.
•
Sender Failure Alarm
•
Display Panel On LED
•
Emergency System Supplying Load LED
•
High Coolant Temperature Pre-alarm
•
Low Coolant Temperature Pre-alarm
•
Low Oil Pressure Pre-alarm
•
Low Fuel Level Pre-alarm
•
Battery Overvoltage Pre-alarm
•
Weak Battery Pre-alarm
•
Battery Charger Failure Pre-alarm
SPECIFICATIONS
RDP-110 Remote Display Panels have the following specifications.
Electrical
Power Input
DC Range
8 to 32 Vdc, 2 watts maximum
AC Range
84 to 144 Vac, 5 VA maximum
Hardware
Communication Port
Interface
RS-485
Used to communicate with DGC-2020, 500, 1000,
and 2000
Isolation
1800 Vdc for one minute between chassis
ground and ac voltage input. 700 Vdc for one
minute between any of the following groups
•
Chassis
ground
•
Battery and 485 terminals
•
AC voltage inputs
Radio Frequency Interference (RFI)
Type tested using a 5 watt, hand-held
transceiver operating at random frequencies
centered around 144 and 440 megahertz with
the antenna located within 6 inches (15
centimeters) of the device in both vertical and
horizontal planes
Environment
Operating Temperature Range
-40°C to 70°C (-40°F to 158°F)
Storage Temperature Range
-40°C to 85°C (-40°F to 185°F)