Changing the fuel type, Generator specifications – Winco ULPSS40/I WITH DSE 7310 ENGINE CONTROL (2014) User Manual
Page 16
![background image](/manuals/716061/16/background.png)
16
4030-00
60706-50
ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY
(GENERATOR)
1. No AC generator output from generator.
. Defective transfer switch controller.
3. Incorrect voltage or frequency from the generator.
4. Wiring error between generator and transfer
switch.
5. Defective mechanically switching solenoid in
Automatic Transfer Switch.
6. Improper phase rotating.
7. Main line breaker on generator open/defective.
ATS PANEL WILL NOT RETRANSFER TO NORMAL POWER
1. Proper normal line power not available at line
terminals in ATS panel.
. Defective transfer switch controller.
3. Defective mechanically switching solenoid in
Automatic Transfer Switch.
4. Retransfer delay still timing out.
NO AC OUTPUT FROM GENERATOR
1. Defective diode.
. Defective voltage regulator.
3. Defective rotor.
4. Defective stator.
5. Defective exciter rotor.
6. Defective exciter stator.
7. AC short in the output leads.
8. Defective field circuit breaker.
CHANGING THE FUEL TYPE
**** CAUTION ****
EQUIPMENT DAMAGE - Do not make any fuel adjustments
or governor adjustments until all pressure readings are in
compliance with specification. See fuel pressure charts (tables
1, 2, and 3).
These engine/generator sets are very easy to convert between
LP or NG. As the engine timing is controlled by the ECU on the
engine you only need to tell it what fuel you want to operate on.
A small rocker switch has been provide on the underside of the
engine control cabinet (see ref L on Page 9) for this purpose.
Opening the rocker switch will tell the ECU mounted on the
engine that you are operating on NG Fuel. Closing the rocker
switch will tell the ECU that the fuel being supplied is LP. The
Advance Power Controller has an idicator light for LP. When this
light is lite the engine is set-up for LP, when the LP light is out the
engine is set up for NG. The ECU will then reprogram the engine
to operate on the proper fuel.
GENERATOR SPECIFICATIONS
PSS21-3
Stanford Newage Model# PI144D1J
(Single phase 4 lead generator)
Winco Part Number
350005-01
Voltage Regulator
AS480
Rotor Resistance
0.657 ohm
Stator Resistance
0.353 ohm
Excitor Stator Resistance 18.5 ohm
Excitor Rotor Resistance 0.8 ohm
PSS21-4/-17/18
Stanford Newage Model# PI144E1L
(Three phase 12 lead reconnectable)
Winco Part Number
350005-013
Voltage Regulator
AS480
Rotor Resistance
0.67 ohm
Stator Resistance
0.300 ohm
Excitor Stator Resistance 19.36 ohm
Excitor Rotor Resistance 0.15 ohm
PSS30-3
Stanford Newage Model# PI144G1J
(Single phase 4 lead generator)
Winco Part Number
350005-011
Voltage Regulator
AS480
Rotor Resistance
0.857 ohm
Stator Resistance
0.13 ohm
Excitor Stator Resistance .5 ohm
Excitor Rotor Resistance 0.01 ohm
PSS30-4/-17/18
Stanford Newage Model# PI144H1L
(Three phase 12 lead reconnectable)
Winco Part Number
350005-007
Voltage Regulator
AS480
Rotor Resistance
0.89 ohm
Stator Resistance
0.171 ohm
Excitor Stator Resistance .90 ohm
Excitor Rotor Resistance 0.10 ohm
PSS40-3
Stanford Newage Model# PI144J1J
(Single phase 4 lead generator)
Winco Part Number
350005-009
Voltage Regulator
AS480
Rotor Resistance
0..983 ohm
Stator Resistance
0.150 ohm
Excitor Stator Resistance .90 ohm
Excitor Rotor Resistance 0.1 ohm
PSS40-4/-17/18
Stanford Newage Model# PI144K1L
(Three phase 12 lead reconnectable)
Winco Part Number
350005-008
Voltage Regulator
AS480
Rotor Resistance
0..99 ohm
Stator Resistance
0.155 ohm
Excitor Stator Resistance .90 ohm
Excitor Rotor Resistance 0.1 ohm