beautypg.com

Viconics H200 User Manual

Page 6

background image

Viconics Electronics Inc.
9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9

www.viconics.com

[email protected]

LIT-H200X-E02 H200.doc

6

"Autocal" button

(Invisible)

1.00" [25mm]

1.275" [32mm]

Cover

1.275" [32mm]

2.8" [71mm]

2.8" [71mm]

3.275" [83mm]

Wiring from top

Security screw

Base

Wiring from back

2.0" [50.8mm]

3.77" [95.8mm]

Cover

0.9" [22.8mm]

1.60" [41mm]

4.5" [114mm]

AUTOCAL PROCEDURE

1. Measure the room humidity near the Viconics

humidistat with an accurate hygrometer.

2. Turn the humidistat set point dial to match the reading

of the hygrometer.

3. Push and hold the autocal button for few seconds or

until the internal red light turns on. Look through the
slots on the left side of the humidistat.

SENSOR FAILURE PROTECTION

The sensor is the most sensitive part of the humidistat and
also the most exposed. In the case of a sensor failure in
humidification mode, the H200 will automatically assume a
failsafe output of 0%.

SPECIFICATIONS

Operating Conditions: 5 °C to 50 °C ( 32 °F to 122 °F )

•Control:

0% to 95% R.H. non-condensing

•Sensor:

0% to 100% R.H. (see Note 1.)

Resolution:

± 0.1 %

Repeatability:

0.5 %

Accuracy and sensor interchangeability:

± 2 % R.H. from 0 to 100 % R.H.

Range:

10 % to 90 % R.H. for 5 to 50 °C
(41 °F to 122 °F )

Temperature effect:

0.05 % / °F

Outputs:

Isolated Triac: 30 Vac at ½ A max.*
0 to 5 VDC into 1K

Ω resistance min.

0 to 10 VDC into 2K

Ω resistance min.

0/5 VDC at 20 mA max.for both outputs

Power:

24 VAC -15%, +10%; 50/60 Hz; 2 VA

Base & casing: Off-white; self extinguishing

ABS plastic

*Triac outputs can only switch AC loads. Use relays when

switching dc loads.

Note 1. Humidity sensor: Solid state humidity sensor.
Suitable for normal, clean air. Not to be used in
corrosive or harmful environment.

DIMENSIONS

Note: Specifications and equipment are subject to change without prior notice.

TABLE 4: SENSOR
CHARACTERISTICS

Voltage between black and white
wire, terminals #6 and #7

HUMIDITY

SENSOR OUTPUT

0 %

1.05 V

5 %

1.19 V

10 %

1.34 V

15 %

1.48 V

20 %

1.63 V

25 %

1.77 V

30 %

1.92 V

35 %

2.06 V

40 %

2.20 V

45 %

2.35 V

50 %

2.49 V

55 %

2.64 V

60 %

2.78 V

65 %

2.93 V

70 %

3.07 V

75 %

3.21 V

80 %

3.36 V

85 %

3.50 V

90 %

3.65 V

95 %

3.79 V

100 %

3.94 V

Fig.8: Dimension drawing