Viconics H200 User Manual
Page 2
2
04/06/04 LIT-H200X-E02 H200.doc
TABLE 1: ORDER CODE
H200
-
A-B
-
C-D
-
E-F
A
Output no. 1 ( controlled device )
1
ON/OFF (15 min. time base)
4
(PWM) 24 VAC
5
(PWM) 5 VDC
6
Analog 0-10 VDC
B
Output no. 2 ( controlled device )
0
Not installed
1
ON/OFF (15 min. time based)
4
(PWM) 24 Volts AC
5
(PWM) 5 Volts DC
6
Analog 0-10 Volts DC
8
Signal transmitter 0-10 VDC
(1V= 10% , 9V-90%)
♦
9
Signal transmitter 0-5 VDC
(0.5V= 10% ; 4.5 V=90%)
♦
C
Output no. 1 and 2 control mode
1
Humidify
2
Dehumidify
3
Humidify ( no. 1 ) and dehumidify ( no. 2 )
4
Dehumidify ( no. 1 ) and humidify ( no. 2 )
D
Main sensor location
Sensor
0
Not installed
None
1
Inside humidistat ( Local )
H50
2
Duct mount ( stat on duct )
H60
3
Duct mount ( stat on wall )
H71
4
Remote wall mount
H80
E
Setpoint adjustment
1
User adjustable
2
Blind cover
F
Future option
0
Unused
Example: H200 - 61 - 32 – 10
One “SCR” 0 to 10 volts humidify output and one relay
dehumidify output.
Humidistat and sensor are duct mount. Setpoint is user
adjustable.
♦ Resolution: 0.5 % for retransmit only
See sensor specifications for dimensions of sensors
Note: the complete order code includes the sensor that will
be shipped with the humidistat.
WIRING
2 ON/OFF OUTPUTS
Single transformer
Fig.2: Wiring diagram with single transformer
Multiple transformers
Fig.3: Wiring diagram with multiple transformers
Note: Both of the above wiring diagrams show how to
wire output of type 1, 2, 3 and 4 (switched 24 Vac).
For outputs of type 5 and 6 (Vdc out) refer to Fig.4 and
Fig.5 on next page.
BLACK
COMMON
6
10
8
9
7
+10 Vdc
MAIN SENSOR
N/A
N/A
INPUT
HUMIDITY SENSOR
FOR CONTROL
RED
WHITE
4
5
1
3
2
OUTPUT #1
ON / OFF
24 Vac
OUTPUT #2
ON / OFF
24 Vac
24 Vac
24 Vac
+
or 24 Vac VALVE
RELAY
-
or 24 Vac VALVE
+
RELAY
-
BLACK
COMMON
6
10
8
9
7
+10 Vdc
MAIN SENSOR
N/A
N/A
INPUT
FOR CONTROL
HUMIDITY SENSOR
WHITE
RED
4
5
1
3
2
OUTPUT #1
ON / OFF
24 Vac
OUTPUT #2
ON / OFF
24 Vac
+
or 24 Vac VALVE
RELAY
-
or 24 Vac VALVE
+
RELAY
-