5

04/06/04 LIT-H200X-E02 H200.doc

SET POINT

50%

db

OUTPUT #1

d2

HUMIDIFICATION

35%

30%

45%

40%

pb

0%

HUMIDIFICATION

100%

OUTPUT #2

100%

0%

d2

OUTPUT #1

DEHUMIDIFICATION

65%

55%

60%

0%

70%

DEHUMIDIFICATION

100%

0%

100%

OUTPUT #2

CONTROL SCHEMATIC:

TABLE 3: H200 PARAMETERS

CODE

VALUES

DEFAULT
VALUE

DESCRIPTION

Db

0 to 40 % R.H.

25% R.H.

Dead Band between humidification and dehumidification.

SL

30 to 100 % R.H.

85% R.H.

Supply Limitation: High humidity limit in the supply duct (H270 only)

d2

0 to 199 % (of proportional
band)

100%

Differential for output #2": Shift for output 2 relative to output 1

Pb

0 = 1.6 % R.H.
1 = 3.2 % R.H.
2 = 6.4 % R.H.
3 = 12.8 % R.H.
4 = 25.6 % R.H.

2= 6.4%
R.H.

Proportional Band

o1

0 = Humidification
1 = Dehumidification

"Output #1" Action for output no 1

o2

0 = Humidification
1 = Dehumidification

"Output #2" Action for output no 2

cc

2 = Without integral
3 = With integral

3

"Control Code"

t1

0 = On/off
1 = 8 minutes
2 = 1 second

"Time #1" Time period for output no 1

t2

0 = On/off
1 = 8 minutes
2 = 1 second

"Time #2" Time period for output no. 2

rA

0 = °C
1 = °F

1 DO NOT
CHANGE

"Range" Temperature Scale

Ca

± 13 %

Calibration ( deviation mode: DO NOT MODIFY: USE AUTOCAL PROCEDURE;
FOR H100 TRANSMITTER, USE THE ZERO POTENTIOMETER ON THE
TRANSMITTER.

hA

0 à 127

"Hardware assembly" Code related to thermostat model and entered at initial setup at
the factory.

it

1 to 99 = 1 TO 99 MINUTES

60

"Integral time" Error integration time.

Lt

-40 à +40 °C (-40 à 105 °F)

-20 °F

"Lower temperature" minimum outside temperature for setpoint reset (model H270 only)

Ht

-40 à +40 °C (-40 à 105 °F)

32 °F

"Higher temperature" maximum outside temperature for setpoint reset (model H270
only)

rE

1 à 99 % R.H.

20 % R.H.

"Reset” Minimum humidity value ( % HR ) (model H270 only)
Example: rE = 20%. Humidity setpoint will be reset from selected setpoint to 20%, from
Ht to Lt

pb = proportionnal band
d2 = differential between output #1 and #2
db = dead band between humidification
and dehumidification

Fig.7: Control schematic