Viconics S3000 Installation Manual User Manual
Page 4
4
Specifications:
General for all sensors
Sensor type:
10 K ohm NTC thermistor
Maximum wire length:
5,000 feet [1,525 m]
for 24 GA wire and up
Room sensors (S3010W1000 and S3020W1000)
Operating conditions:
0
°C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Storage conditions:
-30
°C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Dimensions:
4.94” [125 mm] high
3.38” [86 mm] wide
1.13” [29 mm] thick
Approximate shipping
weight:
0.34 LBS (155 grams )
Enclosure plastic type
ABS - FRI [WT1337V] UV stabilized
Duct sensor (S2000D1000)
Operating conditions:
-40
°C to 50 °C ( -40 °F to 122 °F )
0% to 95% R.H. non-condensing
Storage conditions:
-40
°C to 70 °C ( -40 °F to 122 °F )
0% to 95% R.H. non-condensing
Dimensions:
(refer to drawing Fig.8)
Approximate shipping
weight:
0.7 LBS [0.3 Kg]
Probe tip plastic type:
Fire retarding grade "HB" ABS
Averaging sensor (S2060A1000)
Operating conditions:
-40
°C to 50 °C ( -40 °F to 122 °F )
0% to 95% R.H. non-condensing
Storage conditions:
-40
°C to 70 °C ( -40 °F to 158 °F )
0% to 95% R.H. non-condensing
Sensing element length
72 in [1,83 m]
Sensing element diameter /
material:
3/16” [5 mm] / copper tube
Dimensions:
(refer to drawing Fig.9)
Approximate shipping
weight:
1.6 LBS [0.7 Kg]
Outside air sensor (S2020E1000)
Operating and storage
conditions:
-40
°C to 50 °C ( -40 °F to 122 °F )
0% to 100% R.H.
Dimensions:
(refer to drawing Fig.10)
Approximate shipping
weight:
1.1 LBS [0.5 Kg]
Enclosure plastic type:
NEMA 4 PVC
Duct Mounted Temperature Sensor (S1010D1000)
Operating conditions:
Sensing Bulb Type:
Up
to 85ºC [185ºF]
Plastic Heatshrink
Dimensions:
(refer to drawing Fig.11)
Wire Length:
Probe length / Diameter:
12” [305 mm]
4-1/2” [114 mm]/
1/4” [6 mm]
Important notice
All S1000, S2000 and S3000 series sensors are for use as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the field. Whenever a
control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical
system designer to incorporate safety devices ( such as relays, flow switch, thermal protections, etc…) and/or alarm system to
protect the entire system against such catastrophic failures. Tampering of the devices or miss application of the device will void
warranty.
1/2" [13 mm] FPT
Ø 0.75" [19 mm]
7.00" [178 mm]
1.30" [33 mm]
4.40" [112 mm]
1.75" [44 mm]
2.10" [53 mm]
Ø 5/32" [4 mm]
c/c 1.75" [44mm]
3.38" [86 mm]
1.13" [29 mm]
4.94" [125 mm]
Fig.7
Fig.8
Fig.9
4 .0 0 "
[1 0 2 m m ]
4 .8 8 " [12 4 m m ]
3 .4 5 "
[8 8 m m ]
3 .6 7 " [93 m m ]
* T hre ade d
b ras s ins ert
Ш 8 -3 2 *
Ш 0 .2 5 "
[6 m m ]
Ø 7 /8 "
[2 2 m m ]
1 .6 3 "
[4 2 m m ]
c /c 4 .6 8 " [1 1 9 m m ]
5 .2 5 " [ 13 3 m m ]
1 .1 9 " [30 m m ]
1 .1 9 " [ 30 m m ]
2 .0 0 "
[5 1 m m ]
4 .0 0 " [ 10 2 m m ]
3 .4 5 " [88 m m ]
0 .2 5 " [6 m m ]
2 .1 2 5 "
[5 4 m m ]
Fig. 10
1.75"
[45 mm]
2.25" [57 mm]
4.25" [108 mm]
72" [1829 mm]
Ø 3/16" [5 mm]
FRONT VIEW
7
8
[22]
4
3
8
[111]
WIRE 12 [304]
1
4
[6]
DWG No.: 022-0114.dwg
c/c
13
16
[20]
EYELET FOR MAX.Ш
3
16
[Ш5] SELF-DRILLING SCREW
DATE: 2002/04/19 - REV.0
UNIT: INCH [mm] / NTS
DRAWN BY: P. DUMAS
1
4
[6]
Fig. 11