RTU Commissioning
RTU mechanical cooling functional verification done

Maximum Delta temperature ( return to supply temp ) for cooling stage #1:

Maximum Delta temperature ( return to supply temp ) for cooling stage #1 & 2:

Economizer cooling functional verification done

Minimum position of economizer properly set?

RTU controller Aux output used to disable minimum position of economizer check?

RTU heating functional verification done

Maximum Delta temperature ( return to supply temp ) for heating stage #1:

Maximum Delta temperature ( return to supply temp ) for heating stage #1 & 2:

Static pressure transducer input reading fan Off ( should be 0 “WC or 0 PA ):

Maximum static pressure transducer input reading fan On ( all VAV closed ):

Static pressure damper actuator properly rigged and verified?

Important configuration property set?

-

RTC MAC value:

-

RTC Baud value:

- CntrlTyp:

- Dis

HL:

- Dis

LL:

- H

Lock:

- C

Lock:

- Sp

range:

- Pressure:

Communication with zones is active? ( Status LED & manual scroll display )

Local time clock set?

Local schedule set?

Local system mode set to Auto? ( System On )

Outdoor air sensor properly connected and displaying value? ( manual scroll display )

Supply air sensor properly connected and displaying value? ( manual scroll display )

Return air sensor properly connected and displaying value? ( manual scroll display )


Zone Number ( ) ,
use MAC address for zone name and repeat for ALL other zones
Location:

Date of original installation

VAV inlet diameter Ǿ in Inches:

Zone vocation and use:

Perimeter zone?

VAV actuator brand:

Internal zone?

VAV actuator model:

Type of reheat if installed:

Capacity of reheat if installed:

Zone Configuration, critical operational configuration parameters are in bold
Zone MAC

Unocc HT

RTC Baud

Unocc CL

RTC MAC

St-By

HT

Get From

St-By CL

MenuScro

Set Type

C or F

TOccTime

PIR Func

Cal RS

Lockout

Deadband

BI1

Heat max

RehtConf

Cool min

AO2RA/DA

Min Pos

AO2 OALK

Max Pos

BO5 OALK

MaxHTPos

BO5 Time

PIHT Wei

BO5 cont

PICL Wei

Bold items are critical for proper system operation