Economizer Mode, CO

2

Level Control and Fresh Air Measurement Station



If the fresh air damper is to be used for both free cooling and CO

2

level control with a fresh air

measurement station, only the Min FA, Max FA, Min CO

2

and Max CO

2

parameters as well as the free

cooling sequence will be active.

-

The FA Range parameter should be set to something other than 0 CFM.

-

Use an air flow transmitter to read fresh air level with AI2 input (0-5 VDC input)

-

Min FA, Max FA, Min CO

2

and Max CO

2

parameters should be set according to the required

setting.



Min FA
Setpoint

Max FA
Setpoint

Min CO

2

Max

CO

2

Current
Fresh Air
Setpoint

Current
CO

2

Level

The higher value between free cooling output and interpolation output based on the above graphic will be
the signal sent to the fresh air damper. If the occupancy is unoccupied, then the CO

2

control output will be

0%.