10

configuration.

If the RTU is set to Control Type = Highest demand, the current action delivered by the RTU
will be heating.

If the RTU is set to Control Type = Average of 3 Highest demand, the current action
delivered by the RTU will be cooling.



Example 3 with 5 voting master zones only

Voting

Zone 1

Voting

Zone 2

Voting

Zone 3

Voting

Zone 4

Voting

Zone 5

RTU Control Type

Current heat

demand

Current heat

demand

Current

heat

demand

Current

heat

demand

Current

heat

demand

Highest Average

of 3

highest

Average

of 5

highest

100% 0%

50%%

50%

0%

Heat weight

set

Heat weight

set

Heat

weight set

Heat

weight set

Heat

weight set

100% 100% 100% 50% 100%

Resulting

heat weight

to RTU

Resulting

heat weight

to RTU

Resulting

heat

weight to

RTU

Resulting

heat

weight to

RTU

Resulting

heat

weight to

RTU

100%

0%

50%

25%

0%

100%

58.3%

35%

Current cool

demand

Current cool

demand

Current

cool

demand

Current

cool

demand

Current

cool

demand

0% 100%

0%

0%

100%

Cool weight

set

Cool weight

set

Cool

weight set

Cool

weight set

Cool

weight set

100% 50% 50% 50% 75%

Resulting

cool weight

to RTU

Resulting

cool weight

to RTU

Resulting

cool

weight to

RTU

Resulting

cool

weight to

RTU

Resulting

cool

weight to

RTU

0%

50%

0%

0%

75%

75%

41.7.3%

25%


It can be seen here that the resulting demand used by the RTU controller for the five master voting
zones are different and will result in different heating action simply based on the RTU configuration.

Please note that the heating or cooling action delivered to the zones is also dependent on heating
and cooling lockout functions based on the outdoor and supply air temperature. Please see the next
section for more information.

2B) Overrides and User Zone Interface Lockouts

Each zone controller can have a function locked out for the local user. This can prevent unwanted inputs to
the system as a whole when the zone controllers are installed in public areas or when certain local user
interface functions of the zone controllers are to be prevented.

Lock level is access through the lockout configuration parameter. Please set the appropriate level for each
individual zone in the system according to their requirements.

VZ72xx Controller Lockout Level Configuration Value

0

1

2

3

Local occupied set point access using the Up and Down arrow keys

Yes Yes Yes No

Pressing the local override key will command the local override function only,
However the local heating and cooling demands are not sent to the RTU
controller and the central system will not restart.

Typically used only when perimeter reheat is used and re-started during an
override period.

Pressing the override key allows an override for this zone controller only.

Yes Yes No No

Pressing the local override key will command the local override function and

Yes No

No

No