Communication wiring to vtr73xxa, Terminal equipment controller, Vtr73 – Viconics VC3000 Installation Manual User Manual

Page 4

background image

4 VC7300 Series-Installation Guide

C

OMMUNICATION

W

IRING TO

VTR73

XX

A

T

ERMINAL

E

QUIPMENT

C

ONTROLLER

Only one VC3xxxX relay pack with remote monitoring inputs can be used under a single
VTR73xxA controller. All other slave units must be either VC3xxxX relay pack(s)
WITHOUT remote inputs. A maximum of 10 VC3xxxX relay packs can be used for a
single VTR73xxA terminal equipment controller.

From the VTR73xxA to the first VC3xxxX

o Existing or new field wires

o 3 minimum required 14-22 Ga solid or stranded. Shield not necessary.

7

From the first VC3xxxX to the controller to all other VC3xxxX Relay Pack(s)

o Existing or new field wires

o 2 minimum required 14-22 Ga solid or stranded. Shield not necessary.

o Connect only common and 2 Tx / Rx communication