Viconics VT7200 Installation Manual (Previous Release 5000 Series PIR Ready) User Manual
Page 11
11
Configuration parameters
Default value
Significance and adjustments
Com Addr
Thermostat networking address
Default value = 4
Range is: 0 to 254
Conditional parameter to BACnet MS-TP models (VT7200X1000B)
Conditional parameter to Wireless models (VT7200X1000W)
This parameter will only appear when a BACnet or wireless network adapter is present. If the
thermostat is installed as a stand-alone unit or with an Echelon adapter, this parameter will
not be used or displayed
• For BACnet MS-TP models valid range to use is from 1 to 127
• For wireless models valid range is 0 to 254 with a maximum of 30 thermostat per VGG
PAN ID
Personal Area Network Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to Wireless models (VT7200X1000W)
This parameter will only appear when a wireless network adapter is present. If the thermostat
is installed as a stand-alone unit or with a BACnet or Echelon adapter, this parameter will not
be used or displayed
This parameter (Personal Area Network Identification) is used to link specific thermostats to a
single specific Viconics wireless gateway ( VWG ) For every thermostat reporting to a
gateway ( maximum of 30 thermostats per gateway ), be sure you set the SAME PAN ID
value both at the gateway and the thermostat(s).
The default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID is from 1
to 500
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models (VT720+0X1000W)
This parameter will only appear when a wireless network adapter is present. If the thermostat
is installed as a stand-alone unit or with a BACnet or Echelon adapter, this parameter will not
be used or displayed
This parameter (Channel) is used to link specific thermostats to specific Viconics wireless
gateway(s) ( VWG ) For every thermostat reporting to a gateway ( maximum of 30
thermostats per gateway ), be sure you set the SAME channel value both at the gateway and
the thermostat(s).
Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-2580MHz )
The default value of 10 is NOT a valid channel. The valid range of available channel is from
11 to 26
Get From
Thermostat Get From another device
configuration utility
Default value = 0
Range is: 0 to 254
Conditional parameter to Wireless models (VT7200X1000W)
This parameter / function is not currently supported by the wireless thermostats.
BI1
Binary input no.1 configuration
Default value = None
(None): No function will be associated with the input
(Rem NSB): remote NSB timer clock input. The scheduling will now be set as per the binary
input. It provides low cost setback operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
(Motion NO) or (Motion NC): Advanced PIR occupancy functions using a Normally Open
(NO) or Normally Closed (NC) remote PIR motion sensor. Occupancy mode is now set as
per applied PIR function and configuration. Application information and examples are
available on document: APP-PIR-Guide-Exx. This document will provide the installers and
system designers with detailed examples on applications, parameter configuration
information, sequence of operation, troubleshooting and diagnostic help required for the
proper usage of the PIR accessory covers
(Window) EMS: Forces the system to disable any current heating or cooling action by the
thermostat. The mode stays the same and the current setpoints are the same Occupied
setpoints. Only the outputs are disabled. There is a Door/Window alarm displayed on the
thermostat to indicate to the local tenant that the door/window needs to be closed for cooling
or heating to resume.
* these settings will disable the local override function on the thermostat.