Viconics VT7607 Echelon Integration Guide User Manual
Page 22
22
Manual Identification
Neuron ID of a device can also be entered manually through a commissioning or service tool. Neuron ID
should be located on the Echelon chip of the device being commissioned.
Figure 8 shows an example of a Manual Neuron ID request made through a commissioning tool.
Figure 8: Manual Neuron ID request
Tips And Things You Need To Know
If the heartbeat is lost, the module will release the network sensor value for the Room Temperature
(nviSpaceTemp) and the Outdoor Temperature (nviOutdoorTemp);
The heartbeat parameter of a Tridium front-end should be set at the slowest configuration possible so
that nviTimeStamp updates correctly;
With any LNS Tools, nviTimeStamp should be set to refresh everyday or on power-up;
Viconics recommend to use the provided Viconics format files as stipulated in the snivet per model table
view
Troubleshooting Section
Error / Trouble
Condition
Possible Cause
Solution
The LON network has too many
devices.
Do not exceed the maximum number of
devices and maximum length allowed
by the EIA-485 specifications.
Too many devices were installed
without any repeaters.
Repeaters need to be installed as
specified in this document.
The LON cable runs are broken
Locate the break and correct wiring
Thermostat does not
come online
The thermostat does not have power
Apply power to the thermostat
Document Control
Document Name:
ITG-VT76x7-PIR-LON-E01
Document Filename:
ITG-VT76x7-PIR-LON-E01.pdf
Revision
Date
Changes
00
May 30, 2008
Initial release
02
Feb 06, 2009
Added changes for new PID supported 80:00:C5:55:00:04:04:22
Added revision history table for all VT76x7 PID’s