beautypg.com

Viconics VT7607 Echelon Integration Guide User Manual

Page 14

background image

14

Parameter Variable

Name

Function

This configuration property helps the user identify the type of

equipment being monitored.

Valid Range:

Value

Identifier Name

HVAC Unit-
Type
Identifier

network input config
SNVT_hvac_type
nciHvacType

0
1
2
3
4
5
6
7
8
9

HVT_GENERIC – Not Used
HVT_FAN_COIL
HVT_VAV – Not Used
HVT_HEAT_PUMP
HVT_ROOFTOP
HVT_UNIT_VENT – Not Used
HVT_CHIL_CEIL – Not Used
HVT_RADIATOR – Not Used
HVT_AHU – Not Used
HVT_SLF_CONT – Not Used

Generic
Fan Coil
Variable Air Volume Terminal
Heat Pump
Rooftop Unit
Unit Ventilator
Chilled Ceiling
Radiator
Air Handling Unit
Self-Contained Unit

This configuration property defines model number and software

version of the thermostat

Valid Range and Default values:

Sub

Name

Valid Range

Default value

01

Thermostat Model 00 = VT7657B1000E

17 = VT7607B1000E

Depend on model
being used

Thermostat’s
model number

network input config
UNVT_model_number
nciSccModel

02

Software Version

Unsigned short

Thermostat dependent

Maximum
Send Time

network input config
SNVT_time_sec
nciSendHrtBt

This configuration property defines the maximum period of time that

expires before the specified network variable outputs will automatically
be updated

Valid Range: 0 sec. To 6553.4 sec.. Setting nciSendHrtBt to 0

disables the Send Heartbeat mechanism.

Default Null Value : 0.0 sec (no automatic update)

Minimum
Send Time

network input config
SNVT_time_sec
nciMinOutTm

This configuration property defines the minimum period of time

between automatic network variable outputs transmissions.

Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables

the Minimum Send Time mechanism.

Default Null Value : 0.0 sec (no minimum send time)

Minimum
Receive Time

network input config
SNVT_time_sec
nciRcvHrtBt

This configuration property is used to control the maximum time that

elapses after the last update to a specified network variable input
before the Space Comfort Controller starts to use its default values.

Valid Range: 0 sec. to 6553.4 sec.. Setting nciRcvHrtBt to 0 disables

the Receive Heartbeat mechanism.

Default Null Value : 0.0 sec (no failure detected)

Hardware or
Software
revisions

network input config
SCPT_maj_ver
nciMajVer

This configuration property defines the major module software

revisions.

Valid Range: 0 to 255

Hardware or
Software
revisions

network input config
SCPT_min_ver
nciMinVer

This configuration property defines the minor module software

revisions.

Valid Range: 0 to 255

This manual is related to the following products: