Object name

Object Type

and instance

Under range

value

Over range

value

Default value

Dehumidification Hysterisys

AV 90

2%

20%

5%

Dehumidification Low OA Lockout

AV 91

-40°F (-40°C)

122°F (50°C)

32°F (0°C)

Humidification RH Setpoint

AV 95

10%

90%

50%

Minimum Supply Heat Setpoint

AV 95

50°F(10°C)

72°F(20°C)

64°F(18°C)

Eff (Effective) Reset
Humidification RH Spt (Setpoint)

AV 96

0%

100%

N/A

Supply Heat Lockout
Temperature

AV 96

-15°F(-26°C)

120°F(49°C)

32°F(0°C)

Humidification High Limit Spt
(Setpoint)

AV 97

50%

90%

85%

Supply PI Heat Demand

AV 97

0%

100%

N/A

Low RH Setpoint

AV 98

10%

90%

20%

Minimum Fresh Air

AV 98

0 CFM

20000 CFM

N/A

Low Temp Reset RH Setpoint

AV 99

-40°F (-40°C)

15°F (-9.5°C)

-20°F (-29°C)

Maximum Fresh Air

AV 99

0 CFM

20000 CFM

N/A

High Temp Reset RH Setpoint

AV 100

20°F (-6.5°C)

55°F (13°C)

32°F (0.0°C)

Minimum CO

2

Level

AV 100

0 PPM

2000 PPM

800 PPM

Humidifier Output

AV 101

0%

100%

N/A

Maximum CO

2

Level

AV 101

0 PPM

2000 PPM

1200 PPM