List of Property Value Range Restrictions for AI and AV objects

Object name

Object Type

and instance

Under range

value

Over range

value

Default value

Room Temperature

AV 7

-40°F (-40°C)

122°F (50°C)

N/A

Outdoor Temperature

AV 9

-40°F (-40°C)

122°F (50°C)

N/A

Room Humidity

AV 11

0%

100%

N/A

Supply Temp

AI 16

-40°F (-40°C)

122°F (50°C)

N/A

Supply RH

AV 17

0%

100%

N/A

Water Temperature

AV 17

-40°F (-40°C)

122°F (50°C)

N/A

PI Heating Demand

AV 20

0%

100%

N/A

PI Cooling Demand

AV 21

0%

100%

N/A

Economizer Output

AV 22

0%

100%

N/A

AI1 Value

AI 23

0 VDC

10 VDC

N/A

Analog Heat Output

AV 35

0%

100%

N/A

Occupied Heat Setpoint

AV 42

40°F (4.5°C)

90°F (32°C)

72°F (22°C)

Occupied Cool Setpoint

AV 43

54°F (12°C) 100°F

(37.5°C) 75°F

(24°C)

Unoccupied Heat Setpoint

AV 44

40°F (4.5°C)

90°F (32°C)

62°F (16.5°C)

Fresh Air Level

AI 46

0 CFM

20000 CFM

N/A

Unoccupied Cool Setpoint

AV 45

54°F (12°C) 100°F

(37.5) 80°F

(26.5°C)

Heating Setpoint Limit

AV 48

40°F (4.5°C)

90°F (32°C)

90°F (32°C)

Cooling Setpoint Limit

AV 49

54°F (12°C)

100°F (37.5)

54°F (12°C)

Heating Lockout Temperature

AV 50

-15°F (-26°C)

120°F (49°C)

120°F (49°C)

Cooling Lockout Temperature

AV 51

-40°F (-40°C)

95°F (35°C)

-40°F (-40°C)

Deadband

AV 52

2°F (1°C)

4°F (2°C)

2°F (1°C)

Password Value

AV 59

0

1000

0

Power-up Delay

AV 60

10 sec

120 sec

10 sec

Unoccupied Time

AV 68

0.5 hrs

24.0. hrs

0.5 hrs

CO

2

Level

AI 69

0 PPM

2000 PPM

N/A

Fresh Air Max Range

AV 76

0 CFM

20000 CFM

N/A

Economizer Changeover Setpoint

AV 77

14°F (-10°C)

70°F (21°C)

55°F (13°C)

Economizer Minimum Position

AV 78

0%

100%

0%

Mixed Air Setpoint

AV 80

50°F (10°C)

90°F (32°C)

55°F (13°C)

Economizer Max Position

AV 81

0%

100%

N/A

High Balance Point

AV 82

34°F (1°C)

90°F (32°C)

90°F (32°C)

Discharge High Limit Setpoint

AV 82

70°F (21°C)

150°F (65°C)

120°F (49°C)

Discharge Low Limit Setpoint

AV 83

35°F (2C)

65°F(19C)

65°F (7°C)

Low Balance Point

AV 83

-40°F (-40°C)

30°F (-1°C)

-12°F (-24°C)

Dehumidification RH Setpoint

AV 89

30%

95%

50%

Dehumidification RH Setpoint

AV 89

20%

100%

50%