Phase III

®

27

Model

Boiler Heating

Peak Flow

1st Hour Flow Continuous Flow

Circulator

Capacity MBH

Gal./10 min.

Gal./Hour

Gal./Hour

Min. GPM

TR-20

80

35

125

110

5

TR-30

87

45

140

115

6

TR-36

118

55

190

160

8

TR-45

137

70

220

185

9

TR-60

270

110

410

360

18

TR-80

337

135

510

450

22

TR-100

375

160

575

500

25

TR-120

420

190

650

560

28

Model

Boiler Heating

Peak Flow

1st Hour Flow Continuous Flow

Circulator

Capacity MBH

Gal./10 min.

Gal./Hour

Gal./Hour

Min. GPM

SMART 20

70

35

110

95

5

SMART 30

76

40

125

100

5

SMART 40

106

50

170

140

7

SMART 50

121

65

200

160

8

SMART 60

243

100

370

325

16

SMART 80

285

120

435

380

18

SMART 100

337

150

525

450

25

Conditions:

50º F Domestic Cold Water Inlet Temperature
140ºF Domestic Hot water Outlet Temperature
200ºF Boiler Water Supply Temperature

Performances

Model

Boiler Heating

Peak Flow

1st Hour Flow Continuous Flow

Circulator

Capacity MBH

Gal./10 min.

Gal./Hour

Gal./Hour

Min. GPM

TR-20

105

50

210

190

7

TR-30

120

60

245

220

8

TR-36

145

75

300

270

10

TR-45

190

95

390

350

13

TR-60

335

150

665

620

22

TR-80

365

175

730

670

24

TR-100

400

200

825

750

28

TR-120

445

235

915

820

30

Model

Boiler Heating

Peak Flow

1st Hour Flow Continuous Flow

Circulator

Capacity MBH

Gal./10 min.

Gal./Hour

Gal./Hour

Min. GPM

SMART 20

95

50

195

175

6

SMART 30

115

60

235

210

8

SMART 40

130

70

270

240

9

SMART 50

180

95

370

330

12

SMART 60

320

145

635

590

21

SMART 80

340

165

690

630

24

SMART 100

380

185

775

700

26

Conditions:

50º F Domestic Cold Water Inlet Temperature
115ºF Domestic Hot water Outlet Temperature
200ºF Boiler Water Supply Temperature