beautypg.com

Phase iii, Water heater start-up – TriangleTube TR Series User Manual

Page 23

background image

Phase III

®

20

Water Heater Start-Up

Filling the Inner (Domestic Water) Tank

Never use water heater unless inner and
outer tanks are completely filled with water.

Inner tank must be completely filled and
pressurized before pressurizing outer tank.

1. Close domestic water drain valve.
2. Open domestic water isolation valves for

water heater.

3. Vent air from inner (domestic water) tank by

opening nearest hot water faucet. Fill
domestic water tank completely by allowing
water to run until there is a constant flow of
water.

4. Close hot water faucet.

Filling the Outer (Boiler Water) Tank

Never use water heater unless inner and
outer tanks are completely filled with water.

Inner tank must be completely filled and
pressurized before pressurizing outer tank.

1. Close boiler water drain valve at boiler water

outlet of water heater.

2. Open water heater’s boiler water isolation

valves.

3. Allow air to escape from outer (boiler water)

tank by opening vent cap A on automatic air
vent, located on top of water heater. See Fig.
19.

4. Follow instructions furnished with boiler to

fill with water.

5. When tank is full, air will stop escaping,

and the automatic air vent will close. If air
vent does not seat properly (water leaks
out), remove cap A. Briefly push in valve B
and release it to clean valve seat. Screw cap
A on completely, then unscrew one turn.
See Fig. 19.

For proper operation of the water heater,
always leave vent cap unscrewed one full
turn.

6. If antifreeze is used in boiler water, check

concentration. Boiler water (including addi-
tives) must be practically non-toxic, having
toxicity rating or class of 1, as listed in
Clinical Toxicology of Commercial Products.

Do not use automotive, ethylene glycol or
petroleum-based antifreeze. Do not use any
undiluted antifreeze. This can cause severe
personal injury, death or substantial property
damage.

WARNING

NOTICE

CAUTION

CAUTION

A

B

Automatic Air Vent

Fig. 19:

This manual is related to the following products: