IMPORTANT INFORMATION

The minimum inlet gas supply pressure is 5.5 inches water column for natural gas and 11.0 inches

water column for propane. The maximum allowable inlet gas supply pressure is 10.5 inches water

column for natural gas and 13.0 inches water column for propane. If this appliance is to be supplied

with L.P. gas the tank or bottle supplying the gas must have a regulator that reduces gas pressure

between 11 and 13 inches water column.

WARNING: This appliance must be isolated from the gas supply piping system by closing its

individual manual shutoff valve during any pressure testing of the gas supply piping

system at test pressures equal to or less than 1/2 PSIG.

The appliance and its individual shutoff valve must be disconnected from the gas supply

piping system during pressure testing of that system at test pressures in excess of

1/2 PSIG.

BTU INFORMATION

Set

Natural Gas

L.P. Gas

24”

60,000 BTUs

60,000 BTUs

INSTALLATION TO EXISTING GAS LINE IN FIREPLACE

A manual ON/OFF valve should be present within easy reach of the Gas log set. If a manual valve is

not present, one must be installed prior to the gas log installation.

INSTALLATION IN A MASONRY FIREPLACE

A 1/2” gas supply line must be provided to the fireplace. Most installations require drilling an access

hole through the Masonry wall. The supply line should be secured and sealed by mortar within the

access hole. The supply line should also have an ON/OFF valve in the wall or inside the fireplace.

DAMPER CLAMP INSTALLATION

This appliance is only to be installed and burned in a fully vented fireplace with a fully functional

damper and chimney that is free of any obstructions. A damper clamp is provided to allow any pilot

combustion products to vent. The unit must be operated with the damper in the fully opened position.

(See Figure 1).