beautypg.com

Slant/Fin XL-2000 User Manual

Page 13

background image

BURNER DATA—BECKETT BURNERS FOR PACKAGED BOILERS ONLY

XL-20

(4)

AFG

F0

0.65

0.65

80° A

DELAVAN

100

7

Blank/Closed

3

3/

8

SF2201

XL-30H

AFG

F3

0.85

0.85

70° W

DELAVAN

100

6

Blank/Closed

2

3/

4

SF2204

XL-30

AFG

F3

1.00

1.00

80° W

DELAVAN

100

8

0

2

3/

4

SF2202

1.15

1.00

80° W

DELAVAN

130

10

2

2

3/

4

XL-40H

AF

F6

1.25

1.25

80° W

DELAVAN

100

10

2

None

SF2205

XL-40

AF

F6

1.35

1.35

80° W

DELAVAN

100

10

2

1/

2

None

SF2203

1.55

1.35

80° W

DELAVAN

130

10

5

None

XL-50

AF

F12

1.80

1.75

70° B

DELAVAN

105

10

3

None

SF2207

BOILER

MODEL

BECKETT

BURNER

MODEL

(2) (3)

BECKETT

BURNER

HEAD

FIRING

RATE

NO. 2 OIL

(GPH)

SIZE

(GPH)

ANGLE

AND

TYPE

MFR.

NOZZLES

OIL PUMP

PRESSURE

SETTING

(PSIG)

APPROXIMATE

AIR SHUTTER

SETTING NO.

(1)

APPROXIMATE

AIR BAND

SETTING NO.

STATIC DISK

DIAMETER

INCHES

NOTES:
(1) Blank (closed) air band for XL-20, 2 slot band for XL-30, 4 slot band for XL-40 and 8 slot air band for XL-50.
(2) See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 7 and burner figures on this page.
(3) All burner models shown are single stage.
(4) XL-20 is supplied with a low fire baffle (Beckett No. 31760) installed.

EMBOSSED AIR BAND ADJUSTMENT
OPENS WHEN ROTATED CLOCKWISE
EXAMPLE: SHOWN AT
N

°

2 POSITION

SEE TABLE FOR CORRECT SETTINGS

SHUTTER ADJUSTMENT SHUTTER
OPENS WHEN ROTATED CLOCKWISE
EXAMPLE: SHOWN AT N

°

6 POSITION

AIR BAND
ADJUSTMENT
SCREW

OIL

PU

MP

TOP VIEW OF GUN ASSEMBLY

XL-2000

13