beautypg.com

Slant/Fin XL-2000 User Manual

Page 12

background image

XL-2000

12

BURNER DATA—CARLIN BURNERS FOR PACKAGED BOILERS ONLY

XL-20

99-FRD

0.65

0.65

70° A

DELAVAN

100

0

50

Closed

71399-00F-XL-20

0.65

70° W

DELAVAN

100

0

50

Closed

XL-30

99-FRD

1.00

1.00

70° A

DELAVAN

100

2

80

Closed

71399-00F-XL-30

1.15

1.00

70° A

DELAVAN

130

3

90

Closed

XL-40

99-FRD

1.35

1.35

60° W

DELAVAN

100

4

50

Closed

71399-00F-XL-40

1.55

1.35

60° W

DELAVAN

130

4

65

Closed

XL-50

99-FRD

1.80

1.75

60° B

DELAVAN

105

4

20

Open

71399-00F-XL-50

2.00

1.75

60° B

DELAVAN

130

5

40

Open

BOILER

MODEL

CARLIN BURNER

MODEL (2) (3)

FIRING

RATE

NO. 2 OIL

(GPH)

SIZE

(GPH)

ANGLE

AND

TYPE

MFR.

NOZZLES

OIL PUMP

PRESSURE

SETTING

(PSIG)

“A”

APPROXIMATE

HEAD SETTING

NO.

APPROXIMATE

AIR BAND

OPENING %

(1)

SHUTTER

NON-

ADJUSTABLE

NOTES:
(1) Single slotted air band for XL-20 and XL-30, double slotted air band for XL-40 and XL-50.
(2) See “PRECAUTIONS BEFORE STARTING OIL BURNERS” and “START-UP” on page 7 and burner figures on this page.
(3) All burner models shown are single stage.