GAS PIPING—

A. Local installation codes apply. The pipe joint compound used

on threads must be resistant to the action of liquefied petro-
leum gases.

B. The gas supply line to the boiler should be run directly from

the meter for natural gas or from the fuel tank for L.P.
propane gas. See page 2 for location of union and manual
main shutoff valve that may be specified locally.
Selecting pipe size for natural gas:
1. Measure or estimate the length of piping from the meter

to the installation site.

2. Consult gas supplier for heating value of gas (Btu/cu. ft.).
3. Divide boiler rated input by heating value to find gas flow

in piping (cu. ft. per hour).

4. Use table A to select proper pipe size.
Example: Boiler model S-150 is to be installed. Distance
from gas meter to the boiler is 30 ft. Heating value of natur-
al gas is 1020 Btu/cu. ft. Select proper pipe size.

Gas flow = 150,000 Btu/hour = 147 cu. ft. per hour

1020 Btu/cu.ft.

At 30 ft. length of pipe, match required capacity from Table A
(choose higher capacity, in this case is 152 cu. ft. per hour).
Required pipe size is 3/4".
Improper gas pipe sizing will result in pilot flame outages,
insufficient heat and other installation difficulties. For more
information and also if other appliances are to be attached
to the piping system, see Appendix C of National Fuel Gas
Code ANSI Z223.1-latest edition.

C. The boiler and its gas connection must be leak tested before

placing the boiler in operation. Use liquid soap solution for all
gas leak testing. DO NOT use open flame.
This boiler and its individual shutoff valve must be disconnect-
ed from the gas supply piping system during any pressure test-
ing of that system at test pressures in excess of 1/2 PSIG.
This boiler must be isolated from the gas supply piping sys-
tem by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 PSIG.

D. All gas piping used should be inspected thoroughly for

cleanliness before makeup. A sediment trap must be pro-
vided, as illustrated on page 2.

E. The minimum and maximum gas supply pressure (at the

inlet of gas valve) are shown on the boiler rating plate for the
type of gas used. Gas supply pressure should never be less
than minimum or more than maximum pressure when the
boiler or any other appliance is turned on or off.

ELECTRICAL WIRING

DANGER: Before wiring, always turn off electric power supply,
otherwise, shock or death can result.

1. Power Supply

A separately fused circuit is recommended. Use a standard
15 amp. fuse or breaker and 14 gage conductors in BX
cable or conduit.
Provide disconnect means and overload protection as
required. See boiler wiring diagram (Figure 4).
Boiler must be electrically grounded in accordance with the
requirements of the authority having jurisdiction, or, in the
absence of such requirements, with the National Electrical
Code, ANSI/NFPA 70-latest edition.

2. Power Connection

Connect hot and neutral to L1 and L2 terminal of the
boiler control (See figure 4). Connect ground wire to ground
screw inside boiler control.

3. Thermostat Connections

Thermostat wire connections must be to T and TV screw
terminals of boiler temperature control (See figure 4).
Thermostat Heat Anticipator Adjustments
If the 24V room thermostat that controls this boiler has an
adjustable heat anticipator, connect entire system to thermostat
and run the system while measuring the current drawn through
the thermostat wires. Set the heat anticipator at the value
measured. The set current should match power requirements by
zone valves and relays. Add an additional 0.1 Amp to the
measured current for vent dampers. Refer to the manufacturer’s
instructions of zone valve, vent damper and relays. Also, see
instructions with the thermostat.

4. Multi Zoning

For pump zoning system, see figure 5 and 6 for zone valve
system, see figure 7. DO NOT use control transformer to
power external accessories like zone valve and relay, over
load and/or burned-out transformer and boiler malfunction
can result.

5. Indirect External Water Heater

If the system includes indirect water heater, the indirect signal
must be sepatayed from heating zone(s) system. See figure 6
and 8. Follow steps below:
a. Connect end switch of the indirect water heater relay to I1

and I2 of the boiler temperature control.

b. Connect end switch of the heating zones(s) relays to T and

TV of the boiler temperature control.

c. Power DHW and heating zone(s) circulators through end

switch relays as shown on figure 6. Do not connect heating
zone(s) circulators to C1 and C2 of the control.

Note: For single heating zone with external indirect water
heaters, see figure 9.

1/2

3/4

1

1-1/4

1-1/2

10

132

278

520

1050

1600

20

92

190

350

730

1100

30

73

152

285

590

890

40

63

130

245

500

760

50

56

115

215

440

670

60

50

105

195

400

610

70

46

96

180

370

560

80

43

90

170

350

530

90

40

84

160

320

490

100

38

79

150

305

460

Length
of Pipe

in Feet

Gas Flow In Piping -- cu. ft. per hr.

Iron Pipe Size (IPS)—inches

At pressure drop of 0.3 in. water, specific gravity = 0.60.