GENERAL TROUBLESHOOTING GUIDE FOR SERVICEPEOPLE

BURNERS FAIL TO OPERATE
CAUSE

1. Safety pilot out, or flame too low.
2. Gas supply valve shut off.
3. Electric switch open.
4. Blown or defective line fuse.
5. Operating or limit control contacts open or dirty.
6. Defective gas valve or pressure regulator; or plugged

bleed line.

7. Obstruction at main burner orifice.
8. Break in wiring or loose contact at control terminals.
9. Improper wiring.

10. Improper controls.
11. Rollout or blocked vent safety switch open.

BURNERS WILL NOT SHUT OFF
CAUSE

1. Defective operating control, gas valve, or high limit

control.

2. Improper wiring or short circuit.

FLASH BACK - BURNING AT ORIFICES
CAUSE

1. Manifold gas pressure too low.
2. Improper primary air adjustment.
3. Gas regulator bleed too slow.
4. Burrs on orifice.
5. Improperly drilled orifice plugs.
6. Leaking automatic gas valve.
7. Adverse draft condition in boiler room.
8. Low main gas pressure.
9. Safety pilot improperly installed.

DELAYED IGNITION
CAUSE

1. Pilot flame too low.
2. Pilot burner ports or pilot orifice clogged.
3. Burners or orifices out of alignment.
4. Excessive primary air.
5. Excessive burner input.
6. Adverse draft condition in boiler room.

FUMES AND GAS ODORS
CAUSE

1. Leaks in gas piping or accessories.
2. Gas leaks in service line or meter connections.

3. Blocked chimney.
4. Boiler flueways blocked with soot.

5. Undersized breeching or too many turns in breeching.
6. Adverse draft condition in boiler room.
7. Overfiring.

CONDENSATION IN BOILER FLUES OR IN VENT SYSTEM
CAUSE

1. Underfiring.
2. Boiler water maintained at too low a temperature level.

3. Long horizontal run of smokepipe.
4. Inadequate chimney or venting system.

REMEDY

1. Check, clean, re-light. See instructions.
2. Open gas valve(s).
3. Close switch.
4. Replace fuse.
5. Check control. Clean contacts or replace control.
6. Repair or replace.

7. Check, clean and reinstall.
8. Check with test-light and correct.
9. Check and correct in accordance with wiring diagrams

included with appliance instructions.

10. Install proper controls.
11. Replace rollout switch (inspect flue passages prior to

replacement) or reset blocked vent safety switch by
depressing the reset button.

REMEDY

1. Check, repair or replace.

2. Check wiring and controls.

REMEDY

1. Adjust to proper manifold pressure.
2. Adjust air to produce soft, clean flame.
3. Adjust bleed opening.
4. Remove burrs.
5. Install orifice plugs with proper drilling.
6. Repair or replace.
7. Check air supply and venting system.
8. Contact utility.
9. Correct to manufacturer's recommendations.

REMEDY

1. Increase gas supply to pilot.
2. Clean ports or orifices.
3. Realign burners or manifold.
4. Adjust primary air shutters.
5. Check and reduce to input shown on rating plate.
6. Check air supply and venting system.

REMEDY

1. Locate leaks and repair.
2. Close service supply valve - shut down appliance and

notify utility.

3. Check and repair chimney.
4. Clean flueways and adjust burners as described in the

installation instructions.

5. Check manufacturer's recommendations.
6. Check air supply and venting system.
7. Adjust gas input to that shown on boiler rating plate.

REMEDY

1. Increase firing rate to that shown on rating plate.
2. Set low limit controls to maintain a higher water temper-

ature. If boiler is not equipped with low limit replace
with one which has a combination low limit/high limit
aquastat.

3. Relocate boiler or insulate breeching.
4. Check chimney and venting recommendations.