The installation must conform to the requirements of the authority
having jurisdiction or, in the absence of such requirements, to the
National Fuel Gas Code, ANSI Z223.1-latest edition.

This installation must also conform to the additional requirements
in this Slant/Fin Instruction Book.

NATURAL GAS-FIRED BOILER LOCATION

Provide a level, solid foundation for the boiler. Location should be
as near as possible to chimney or outside wall so that the flue pipe
from boiler is short and direct.

The location should also be such that the gas ignition system com-
ponents are protected from water (dripping, spraying, rain, etc.)
during appliance operation and service (circulator replacement,
condensate trap, control replacement, etc.).

BOILER FOUNDATION

A. Provide a solid, level foundation, capable of supporting the

weight of the boiler filled with water, and extending at least 2"
past the jacket on all sides. See dimensions of boiler, page 2.

B. For installation on non-combustible floors only. The

Combustible Floor Kit part number printed on the boiler rating
plate is the only one to be used when installing on combustible
floors. The boiler must not be installed on carpeting.

C. If boiler is to be located over buried conduit containing electric

wires or telephone cables, consult local codes or the National
Board of Fire Underwriters for specific requirements.

S-34

2

8

1

8

"

14

5

8

"

4

33"

6

1

4

"

190

S-60

3

11

1

8

"

17

5

8

"

4

37"

4

1

2

"

26"

6

1

4

"

250

S-90

4

14

1

8

"

20

5

8

"

5

37"

5

1

2

"

25

1

2

"

6

1

4

"

310

S-120

5

17

1

8

"

23

5

8

"

6

37"

7

1

2

"

25"

6

1

4

"

365

S-150

6

20

1

8

"

26

5

8

"

7

37"

8

1

2

"

24

1

2

"

8

1

4

"

425

Boiler
Model

Gas

Type

2000

3000

4000

5000

6000

7000

8000

9000

10000

Orifice

Size for

Sea

Level

Orifice Sizes for High Altitudes

Includes 4% Reduction for Each 1000 Feet

Elevation - Feet

No. of

Sect.

Dimensions

(inches)

A

B

C

D

E

F

G

(max)

Approx.

Total Wt.

Full of

Water (lb.)

Natural

47

48

48

49

49

49

50

50

51

51

Propane

56

56

56

57

57

57

58

59

59

60

Natural

50

51

51

51

51

52

52

52

53

53

Propane

57

58

59

59

60

60

61

62

63

63

CHIMNEY RECOMMENDATIONS

HEIGHT:15 ft. (minimum) from draft
hood skirt to top of chimney.
INSIDE DIAMETER: Same as dimen-
sion C (or larger).
NOTE: Larger chimney may be
required if two or more boilers or a boil-
er and another appliance are vented to
a single chimney.
Slant/Fin supplies vent dampers by
several manufacturers. Some are
smaller than the indicated “G maxi-
mum”.

Orifice indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority.
See page 20 for burner input adjustment.

Boiler
Model

S-34

S-60 thru S-150

Base Assembly
Sentry Boiler

Burners

Pilot

Burner
Access
Door

Gas Valve

INSTALLATION REQUIREMENTS