SEQUENCE OF OPERATION FOR SENTINEL BOILERS

THERMOSTAT CALLS FOR HEAT

HIGH LIMIT CONTACTS CLOSED?

LOW WATER CUT-OFF

CONTACTS CLOSED?

VENT DAMPER RELAY ENERGIZED.

VENT DAMPER MOTOR OPENS VENT DAMPER.

END SWITCH CLOSES.

IGNITION CONTROL ENERGIZED

THE PILOT FLAME ESTABLISHED ?

SPARK GENERATOR OFF. MAIN VALVE

OPERATOR OPENS. MODULE MONITORS

PILOT FLAME.

WHEN THERMOSTAT IS SATISFIED OR WHEN HIGH LIMIT OR LOW WATER CUT-OFF CONTACTS ARE OPEN, VALVE OPERA-

TORS CLOSE. PILOT and MAIN BURNERS OFF. VENT DAMPER CLOSES. CIRCULATOR OFF. SYSTEM GOES TO STANDBY.

SPARK GENERATOR MODULE POWERED.

S8600F OR S8600M: IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS.

S8670E: IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30-70 SECONDS.

L.P. PROPANE GAS (S8600M and
S8670E) IGNITION TRIAL CONTINUES
FOR 90 SECONDS. AFTER TRIAL FOR
IGNITION, SYSTEM SHUTS OFF.
AFTER 5 MINUTES MODULE RE-
INSTATES TRIAL FOR IGNITION. IF
PILOT FLAME NOT ESTABLISHED,
IGNITION TRIAL, SYSTEM SHUT-OFF
AND 5 MINUTES WAIT SEQUENCE
REPEATS CONTINUOUSLY.

NATURAL GAS (S8600F) IGNI-

TION SPARK CONTINUES.

PILOT VALVE REMAINS OPEN

UNTIL SYSTEM IS RESET.

CIRCULATOR ENERGIZED

NO FURTHER

ACTION

YES

NO

YES

NO

NO