beautypg.com

Troubleshooting, Led legend and lwco test button – Slant/Fin 3000-190 User Manual

Page 6

background image

6

HI TEMP

Illuminates when the

boiler water temperature reaches the

high limit setting. It will remain lit until

the water temperature falls 10° (see

High Limit Differential on page 5). The

Fuel Smart HydroStat prevents burner

operation while this

LED is on.

LWCO ACTIVE

Indicates that

the low water cut-off (LWCO) function

of the Fuel Smart HydroStat is active.

When the control is installed with a

Hydrolevel Electro-Well, this LED will

be on at all times when the control is

powered. IMPORTANT: If the control is

installed with a well other than the

Electro-Well, this LED will not illuminate

indicating that the control is not providing

low water cut-off functionality.

LWCO LOW WATER

Illuminates if the boiler is in a

low water condition. The Fuel Smart HydroStat will prevent

burner operation during this condition. IMPORTANT: The

system must be checked by a qualified heating professional

prior to resuming operation.

WARNING: DO NOT ADD WATER UNTIL THE

BOILER HAS FULLY COOLED.

ECONOMY ACTIVE

Indicates that the Thermal

Targeting function is active and the Fuel Smart HydroStat will

reduce boiler temperature to conserve fuel. The Economy

feature is activated using the ECONOMY dial. (See “How

Thermal Targeting Works” on page 5 for more information).

ECONOMY TARGET

When

the Economy feature is active, the

Fuel Smart HydroStat continually sets

target temperatures below the high

limit setting to maximize fuel

efficiency. When the boiler water

reaches the target temperature, the

LED illuminates and the burner will

shut down. The boiler water will

continue to circulate and heat the

house as long as the thermostat call

continues. The LED will stay lit until

the boiler temperature drops below

the differential (see Differentials on

page 5) at which point the boiler will

be allowed to fire again. NOTE: This

LED illuminates regularly during

normal boiler operation.

PURGE

The control is purging latent heat from the boiler and will not

fire until the temperature drops to 135°F. See page 5 for

additional information on Thermal Pre-Purge.

LWCO TEST Button

To Test Low Water Cut-Off: Press and hold the LWCO

TEST button.
The red Low Water light should illuminate and the burner

circuit should de-energize. NOTE: The control must be

installed with a Hydrolevel Electro-Well for low water cut-off

functionality (see page 2 for more details).

TROUBLESHOOTING

Burner Will Not Fire

See Flow Chart, page 7

No or Insufficient

Domestic Hot Water

If installed with an indirect water heater, insure that the end switch in the relay box

controlling the indirect water heater is properly connected to Cable 2 (see wiring steps 3

and 4 on page 3). This will insure that the domestic water calls are prioritized. If Cable 2

is not used, turn the Economy Feature OFF.

House Will Not Get

or Stay Warm

1. Check for air-bound radiators. 2. Check thermostat settings including heat anticipator

settings (common on non-digital thermostats). 3. Check the Economy setting. The

Economy feature, much like outdoor reset controls, lowers average boiler temperature

and can slow or the house from coming up to temperature. Move to a lower setting (see

“Setting the Economy Feature” on page 5).

Low Water Light

(Red LED) is On

WARNING: A low water condition is a serious and potentially dangerous condition. Do not

attempt to add water to a hot boiler. Allow the boiler to fully cool before adding water.

The LOW WATER light indicates that the control is not detecting water in the boiler.
1. If the light is on and the heating system is filled with water, pull the sensor out of the well and

inspect it. Make sure that the metal clip on the sensor is intact. This metal clip must be in contact

with the inside of the copper well in order for the control to sense the presence of water. Check

that the well does not have excessive build-up of heat transfer grease that may interfere with clip

contacting the well.

2. Remove well and examine for excessive residue build-up. Clean and re-install.

LED LEGEND and LWCO TEST BUTTON

Model 3000 shown above.

Model 3000-190 has 190° max high limit.

This manual is related to the following products: