Warning – Slant/Fin 3000-190 User Manual
Page 4

4
WARNING
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
WIRING TO IGNITION CONTROL MODULE
TO
INDIRECT
WATER
HEATER
FROM
THERMOSTAT
INPUT ON
CONTROL
MODULE
#45-531-56
Wire
Harness
For use on boilers equipped with Integrated Boiler Control Module
CABLE 1 — ቢ Disconnect boiler wire Harness from the “SECONDARY” port on the Integrated Control Module
and ባ plug into female plug adapter on #45-531-56 Wire Harness. ቤ Plug male adapter on #45-531-56 Wire
Harness into “SECONDARY” port on the Integrated Control Module. ᕆ Plug the other end of the Wire Harness
into the Model 3000 Low Water Cut-Off. ᕇ Connect the yellow wires in series with Limit Circuit.
CABLE 2 — ቨ Plug Wire Harness into the Model 3000 Low Water Cut-Off. ቩ Connect the two YELLOW wires
to the end switch from the indirect water heater relay. NOTE: If you are not connecting to an indirect water heater,
the bare ends of the YELLOW wires must be capped off separately with wire nuts. ቪ Connect the RED and WHITE
wires in parallel to wiring from the thermostat input on the control module and the existing thermostat wiring.