beautypg.com

Slant/Fin 3000-190 User Manual

Page 5

background image

Setting the High Limit

The high limit is factory set at 190°F. To adjust,

turn the HI TEMP Dial

to the desired setting.

Setting range: Model 3000 – 100°-220°F

Model 3000-190 – 100°-190°F

Setting the Economy Feature

The Economy Feature is factory set for a 1 zone heat-

ing system. To adjust, turn the ECONOMY Dial

to

the number of heating zones. Do not include indirect

water heaters in the number of heating zones. The

Economy Feature conserves fuel by reducing boiler

temperature (see “How Thermal Targeting Works”

below). If the heating system is unable to supply need-

ed heat to the house, the ECONOMY Dial should be

turned to a lower setting (example: In a three zone

house, turn the dial to 2 or 1). Conversely, if the boiler pro-

vides adequate heat, added fuel savings can be achieved by

selecting a higher setting (example: 4 or 5). If the heating

and indirect water heater signals were not separated when

wiring the control or if you do not use optional Cable 2, the

Economy Feature must be turned OFF to insure the boiler

supplies adequate temperature to heat the indirect tank.

Differentials

Differentials are automatic and will vary based on

control settings and boiler temperature.

5

SETTING THE CONTROL

HOW THERMAL TARGETING WORKS

SYSTEM START-UP

Thermal Targeting technology analyzes thermostat activity and continually evaluate how much heat the house requires. When it

is very cold outside, the heat demand is high and the Fuel Smart HydroStat will raise the boilerʼs Target temperature to provide

needed heat to the home. When the outside temperature is milder, the heat demand is lower. During these periods, the Fuel

Smart HydroStat will lower the boilerʼs Target temperature – saving fuel – while continuing to provide comfort to the house

.

SETTING

OFF Disables economy function. Will allow boiler to fire until hi-

limit temp is reached and re-fire with a 10° subtractive
differential.

LO Provides lowest level of fuel savings. Use this setting only if

the house does not stay warm at higher settings.

1

Recommended setting for single zone systems

2

Recommended setting for Two zone systems

3

Recommended setting for Three zone systems

4

Recommended setting for Four zone systems

5

Recommended setting for Five zone systems

HI

Provides highest level of fuel savings

Activating Thermal Pre-Purge (optional)

Fuel Smart HydroStat has a Thermal Pre-Purge feature to

maximize efficiency. When active, the control will purge higher

boiler temperatures down to 135° at the start of any thermo-

stat call and supply the latent energy in the boiler to the heat-

ing zone that is calling. During the purge cycle, the PURGE

LED will light. If the heat is not sufficient to satisfy the thermo-

stat, the control will energize the burner. This feature works

with single-zone and multi-zone heating systems utilizing cir-

culators or zone valves. No change in wiring is needed.

To Activate Thermal Pre-Purge

Push and hold the LWCO TEST button for 10 seconds. The

PURGE LED will blink twice and remain on as long as your

finger is on the button. To deactivate the feature, push and

hold the button a second time for 10 seconds. The PURGE

LED will blink twice and turn off.

At initial start up, with the Economy Feature active, the control establishes a 145°F target temperature. To test the high limit

shut-off function, the Economy Dial must be turned to OFF. Once tested, restore the Economy setting. If the heating demand is

high, the target will increase over time to satisfy the heat load.

190

175

16

0

14

5

130

115

Model 3000

Model 3000-190

This manual is related to the following products: