Slant/Fin 3000-190 User Manual
Page 2
2
MOUNTING THE CONTROL
STEP 1
Insert sensor ALL THE WAY into well. (Fig. 1)
STEP 2
Place control on the well.
While holding box against well nut,
tighten well clamp screw. (Fig. 2)
FIG. 2
FIG. 1
NOTE: In the case of space restrictions,
the Fuel Smart HydroStat control may
be mounted in a horizontal orientation
without any loss of function.
IMPORTANT
Make sure that the immersion well or Electro-Well™ is installed in the boiler manufacturer’s designated
temperature limit control tapping.
N
NO
OT
TE
E:: If installing an Electro-Well, pipe sealing compound should be used. Teflon tape is not recommended.
IMMERSION WELLS
IMPORTANT: For proper operation of the low water cut-off function, there
must be a minimum of ½" clearance between the copper well tube and any
surface within the boiler.
See Electro-Well models on page 8.
NOTE: When installed on a standard immersion well, the “LWCO Active”
LED will not illuminate.
Fuel Smart HydroStat can be installed on an existing immersion well already in the boiler or on a Hydrolevel Electro-Well™
(sold separately). The low water cut-off function is automatically activated when installed on an Electro-Well™.
IMPORTANT: The control will not provide low water cut-off protection when installed on a standard immersion well.
NOTE: Do not use heat-conducting grease.
Fuel Smart HydroStat installed
with Hydrolevel Electro-Well™
Fuel Smart HydroStat installed
with standard immersion well