13 - use – Slant/Fin VSL-160C Part C User Manual
Page 5

77
13 - USE
PARAMETER DESCRIPTION
INFORMATION ON DISPLAY ITEM “2” OF FIGURE 13-1
Can be changed (see Section 13.9):
00 = thermostatic adjustment;
01 = outdoor reset;
02 = outdoor reset with room compensation;
Keep always at value of 1
Can be changed from 16°F (-9°C) to 149°F (65°C) (active only with
outdoor reset).
See section 13.10.3 for its adjustment.
Can be changed: from 1°F (1°C) to 36°F (20°C) (active only with
outdoor reset featuring room compensation)
See section 13.10.6 for its adjustment.
Can be changed:
01 = knobs presents;
00 = knobs absent.
Can be changed: 00 = display always on; any other value,
corresponds to a delay in the switching off of the display, expressed
in minutes (see also Section 13.15)
No infl uence in this kind of boiler
No infl uence in this kind of boiler
Must be maintained at 20 value
Must be maintained at 40 value
Can be changed between 1 and 54. Default value is 18 (180 sec).
Can be modifi ed only in conjunction with factory technicians.
Can be changed between 00 (function disabled) and 99 minutes.
Default value is 00 (See also section 9.1.1).
Heating service functioning mode
Reaction to external temperature
Angle fulcrum of climatic adjustment
Reduction of temperature generated by
the opening of the room thermostat
Boiler knobs’ status
Display “1” and “2” as per fi gure 13-1
energy saver
Parameter disabled for this kind of boiler
Domestic sensitivity setting
Minimum domestic setpoint during sleep
mode
Proportional band of the heating PID
modulation
Integral of the heating PID modulation
Burner Anticycling: minimum delay from
a burner light-off to the sequent light-on.
Value expressed in sec x 10
Indirect water heater priority selection:
Value expressed in minutes.